LEOPARD FAMILY
General Features
External transmitters or signal conditioners can be eliminated
by direct connection of the sensor output to more than
38 Plug-in Input Signal Conditioners that include:
AC/DC Current Pressure AC/DC Voltage Process Load Cell
Prototype
Resistance
*Temperature
4 to 20 mA
*See model BL-40H for higher accuracy digitally linearized
thermocouple and RTD
Optional isolated 6 bit analog output. User or factory scalable to 4 to 20 mA, 0 to 20 mA or 0 to 0 V across any desired digital span from one count to the full scale range of 999 to 9999 (2000 counts).
Auto-sensing AC/DC power supply. For voltages between
85-265 V AC / 95-370 V DC (PS1) or 5-48 V AC / 0-72 V DC (PS2).
24 V DC excitation is available to power external transmitters and 5 or 0 V DC excitation is available for resistance bridge type sensors such as Load Cells and Pressure Transducers.
Standard red or optional green or super bright red 4-digit LED
with display range 999 to 9999 (2000 counts).
Three annunciator LEDs provide front panel alarm status
indication for up to three setpoints.
One 0 Amp Form C and one 5 Amp Form A relay, or up to
three 5 Amp Form A relays are available.
When analog output is installed, one 0 Amp Form C or two 5
Amp Form A relays can be supported.
Automatic intelligent averaging smooths noisy signals, while providing a fast display response to real level changes.
Three-button programming from the front panel
(UP, DOWN and PROGRAM buttons).
Three front panel selectable ranges.
Front panel selectable four-level brightness control of digital dis-
play, and setpoint LEDs.
Three programmable setpoints.
Relay activation can be selected to occur above (HI) or below
(LO) each setpoint.
Hysteresis setting for all three setpoints. Delay on make and
delay on break for SP and SP2.
Peak and Valley. View and Reset.
LEOPARD FAMILY: More than 38 different Plug-in I-Series Modular Input Signal Conditioners are approved for Texmates Leopard Family of meters. Some examples are shown on pages 0-2.
See www.texmate.com for an up to date listing.
Specifications
Input Specs:..............Depends on input signal conditioner A/D Converter:...........4 bit single slope Accuracy:...................(0.05% of reading + 2 counts) Temp. Coeff.:.............00 ppm/C (Typical) Warm up time:...........2 minutes Conversion Rate:......5 conversions per second (Typical) Display:......................4 digit 0.56" Red LED display (std), 0.56 Red, Green or Super Bright Red (optn). Range 999 to 9999 counts.
Polarity:......................Assumed positive. Displays negative Decimal Selection:....Front panel button selectable, XXXX Positive Overrange:..Top segments of digital display flash Negative Overrange:.Bottom segments of digital display flash Relay Output:............Three 5 Amp Form A relays or one 0 Amp
Form C, and one 5 Amp Form A relay.
Analog Output:..........Isolated 6 bit user scalable mA or V OIC (mA out)...........4-20 mA @ 0 to 500 max loop resistance OIV (volts out).......... 0-0 V DC @ 500 or higher resistance Power Supply:...........AC/DC Auto sensing wide range supply PS1 (std)................85-265 VAC / 95-370 VDC @ 2.5W max 3.2W PS2.........................5-48 VAC / 0-72 VDC @ 2.5W max 3.2W Operating Temp.:.......0 to 60 C Storage Temp:...........20 C to 70 C.
Relative Humidity:....95% (non condensing) Case Dimensions:...../6 DIN Bezel 96x24mm
Depth behind bezel 22.2mm (4.83") Plus 2.7mm (0.5) for Right-angled connectors
Weight:.......................7 oz, 9 oz when packed
BL-40PSF DS (BL5)
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
Page
Program lockout header
behind face plate.
SP3
SP2
PROGRAM
BUTTON P
UP ARROW
BUTTON
DOWN ARROW
BUTTON
To explain software programming procedures, logic diagrams are used to visually assist in following the programming steps. The fol-lowing symbols are used throughout the logic diagrams to represent the buttons and indicators on the meter:
Symbol
Explanation
This symbol represents the OPERATIONAL DISPLAY.
This is the PROGRAM button.
This is the UP button.
This is the DOWN button.
When a button is shown, press and release it to go onto the next step in the direction indicated by the arrow. When two or more buttons are shown, each with an arrow, this indicates that there is a number of programming choices.
When two buttons are shown side by side and enclosed by a dotted line, they must be pressed at the same time then released to go onto the next programming step.
If the display is shown with XXXX it means the value displayed will be the previously set value. When a number is shown it indicates the initial factory default setting or a specific example number.
Program Button
The P button is used to move from one program step to the next. When pressed at the same time as the button, it initiates the calibration mode. When pressed at the same time as the button, it initiates the setpoint setting mode.
Up Button
When in the operational display, pressing the button alone, allows you to view and reset the Peak and Valley (Highest and Lowest Readings.)
When in the calibration mode or the setpoint setting mode the button is used to increase the value of the displayed parameter.
Down Button
When in the operational display, pressing the you to view, but not change, the setting of setpoint , 2 and 3.
button alone, allows
When in the calibration mode or the setpoint setting mode the button is used to decrease the value of the displayed parameter.
When two displays are shown together
with bursts, this indicates that the display is
toggling (flashing) between the name of the
function and the value.
[Span]
Text or numbers shown between square
brackets in a procedure indicate the pro-
[10000]
gramming code name of the function or the
value displayed on the meter display.
When the
and
buttons are shown
together, the display value can be increased
by pressing and releasing the
button
or decreased by pressing and releasing the
button.
When the
and
buttons are shown
with two displays, either display can be
selected by pressing and releasing the
buttons.
When there are more than two display selec-
tions they are shown in brackets below the
first display and are also selectable by press-
ing and releasing the
buttons.
A dotted box indicates these functions are
omitted or bypassed when the related hard-
ware is not present
Page 2
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
BL-40PSF DS (BL5)
The BL-40PSF is an intelligent meter with a hierarchical software structure designed for easy programming and operation, as shown below in the software logic tree.
After the meter has been powered up, the four digits light up for three seconds and then settle to the operational display indicating the input signal.
15 Second Program Timeout The meter has a 5 second program timeout. If no buttons are pressed for 5 seconds, at any stage of the programming sequence the meter will exit the programming mode and return to the operational display. Any program changes that were made prior to pressing the P button in the preceding step will not be saved.
BL-40PSF DS (BL5)
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
Page 3
The DL-40PSF meter may be rescaled without applying an external signal by changing the Offset and Scale factor.
Offset is the reading that the meter will display for a zero input. The Offset may be set to any value from -999 to +9999. The default value of the Offset is 0
Scale factor is the gain of the meter. The displayed reading is directly proportional to the Scale factor. The default value of the scale factor is 2000, but it may be set to any value between -999 and +9999.
For an input of 2V a calibrated meter will read 2000 with the default Scale factor of 2000, 3000 with a Scale factor of 3000 and 500 with a Scale factor of 500
If a linear scale is represented by mx + b, then the Scale Factor corresponds to the slope m and the Offset corresponds to the intercept b
The internal Signal Span is limited to 3 V DC between V DC to + 2 V DC. Outputs from an Input Signal Conditioning module that exceed these limits will cause the meter to indicate overrange.
Note: Most input signal conditioners have provisions for analog calibration and scaling. If the meters digital Scale Factor is set to
2000 and Offset set to 0 then, any pre-calibrated signal conditioner with an output that does not exceed V to + 2 V, will read correctly in the meter without any further calibration.
STEP A Enter the Calibration Mode ) Press the P and Display toggles between [cAL] and [oFF].
2) Press the
Display changes from [oFF] to [on].
3) Press the P button. Display toggles between [cAL] and [out].
buttons at the same time.
button.
STEP B Select Between Calibration of Input or Output
Note: If the analog output option is not present, Step B is skipped and the program goes directly from Step A to Step C.
) Press the
to [iP].
button to select the display toggling from [cAL]
2) Press the P button. Display toggles between [oFFS] and the previous offset setting.
STEP C Set the Offset on the Digital Display
) Using the
desired offset. This is the reading that the meter will display for a
buttons, adjust the digital display to the
and
zero input
2) Press the P button. Display toggles between [ScAL] and the previous Scale factor.
STEP D Set the Scale factor on the Digital Display and
) Using the
desired Scale factor. The default value is 2000, for which a 2V
buttons, adjust the meter display to the
input will read 2000. If the scale factor is changed the display will change proportionately. Therefore if the Scale factor is changed to
000 then for the same 2V input the display would read 000.
3) Press the P button.
The Digital Calibration Procedure Mode is Now Complete.
The menu branches to the DECIMAL POINT AND BRIGHTNESS SE LECTION, (see page 5) and the display flashes [dP] and the previous decimal point selection.
Page 4
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
BL-40PSF DS (BL5)
STEP A Enter the Calibration Mode ) Press the P and Display toggles between [cAL] and [oFF].
2) Press the
3) Press the P button. Display toggles between [cAL] and [out] input calibration.
button. Display changes from [oFF] to [on].
buttons at the same time.
Note: If at this point the display skips directly to toggle between [SPAn] and the previous [SPAn], the software is detecting that the optional analog output hardware is NOT installed.
STEP B Enter the Analog [oUT] Output Mode
) Press the P button. Display toggles between [cLo] and an internal scale factor.
STEP C Set or Calibrate the [cLo] Low Analog Output Range
) Select the voltage or current loop output header position on the output module. (See Component Layout on page 9).
2) Connect a multimeter to pins 8 and 9 on the output module. (See Rear Panel Pinouts on page 8). Using the
buttons, adjust the analog
and
output to the desired low value as shown on the multimeter display.
CLo may be adjusted to any value from 0.3 mA to 7 mA (mA output
selected) or from 0.6 V to 8 V (volt output selected)
3) Press the P button. Display toggles between [Chi] and an internal scale factor.
STEP D Set or Calibrate the [chi] High Analog Output Range
) Using the
and
buttons, adjust the analog output to the desired high
value as shown on the multimeter display. chi may be adjusted to any value
from 7 mA to 2 mA (mA output selected) or from 8 V to 0.3 V (volt
output selected)
2) Press the P button. The display exits the calibration mode and returns to
the operational display.
Note: Having established the Low and High range of the analog output, the digital span can now be selected which will set the two digital points between which the analog output will occur. (See Digital Span Selection below).
STEP A Enter the Decimal Point and Brightness Mode Through the Sub Menu
[cAL] [oFF]
) Press the P and Display toggles between [cAL] and [oFF].
2) Press the P button. Display shows previous [dp] selection.
buttons at the same time.
STEP E Set the Decimal Point, adjust the display to the desired decimal point setting. ) Using the 2) Press the P button. Display toggles between [Br] and the previous [Br] setting.
and
STEP F Set the Display Brightness
) Using the
and
buttons, adjust the display to the desired brightness
setting (4 is the brightest setting).
2) Press the P button. Display brightness changes to new setting and display
toggles between [AnHi] and the previous [AnHi] setting.
STEP G Setting the Digital Span Point for Analog High Output
buttons, adjust the display to the desired digital value ) Using the which sets the point at which the selected analog high output range will occur.
2) Press the P button. Display toggles between [AnLo] and previous [AnLo] setting.
and
STEP H Setting the Digital Span Point for Analog Low Output
buttons, adjust the display to the desired digital value ) Using the which sets the point at which the selected analog low output range will occur.
2) Press the P button. The display exits the calibration mode and returns to
and
the operational display.
Note: Any two digital scale points from 999 to 9999 can be selected. The digital scale points for analog high and analog low can be reversed for reversed 20-4 mA output. The span of the digital scale can be as small as two counts however small spans cause the 6 bit D to A to increment in stair case steps.
BL-40PSF DS (BL5)
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
Page 5
The following programming steps are required to enter the setpoint values and configure the relay functions in a meter with four relays using four setpoints. Generally if less than four relays are installed the software auto detects missing relays and deletes reference to them from the menu. In some cases setpoints without relays are operational for display only purposes.
STEP A Enter the Setpoint Mode
) Press the P and Display toggles between [SP] and the previous [SP] setting.
buttons at the same time.
STEP B Set Setpoint 1 (SP1) ) Using the and 2) Press the P button. Display toggles between [doM] and the previous [doM] setting.
buttons, adjust the display to the desired SP value.
STEP C Set the SP1 Delay-on-Make (doM) Delay Time Setting
) Using the
and
buttons, adjust the display to the desired [doM] value
(0 to 9999 seconds). The reading must continuously remain in an alarm condition until this delay time has elapsed before the relay will make contact (energize).
2) Press the P button. Display toggles between [dob] and the previous [dob] setting.
STEP D Set the SP1 Delay-on-Break (dob) Delay Time Setting
) Using the
and
buttons, adjust the display to the desired [dob] value (0 to 9999 seconds). The reading must continuously remain in an non-alarm condition until this delay time has elapsed before the relay will break contact (de-energize).
2) Press the P button. Display toggles between [HYSt] and the previous [HYSt] setting.
STEP E Set the Hysteresis Setting for Setpoint 1
and
) Using the
2) Press the P button. Display toggles between [SP2] and the previous [SP2] setting.
NOTE: Half of the Hysteresis value selected is applied above and below the setpoint.
buttons, adjust the display to the desired hysteresis [HYSt] value.
NOTE: Steps F, G, H and J have functionally the same procedure as steps B, C, D, and E shown above.
STEP F Set Setpoint 2 (SP2) STEP G Set the SP2 Delay-on-Make (doM) Delay Time Setting STEP H Set the SP2 Delay-on-Break (dob) Delay Time Setting STEP I Set the Hysteresis Setting for Setpoint 2
) Using the
2) Press the P button. Display toggles between [SP3] and the previous [SP3] setting.
buttons, adjust the display to the desired hysteresis [HYSt] value.
and
STEP J Set Setpoint 3 (SP3) (No [doM] or [dob])
) Using the
2) Press the P button. Display toggles between [HYSt] and the previous [HYSt] setting.
buttons, adjust the display to the desired SP3 value.
and
STEP K Set the Hysteresis Setting for Setpoint 3
) Using the
2) Press the P button. Display toggles between [rLYS] and the previous relay setting.
buttons, adjust the display to the desired hysteresis [HYSt] value.
and
STEP N Set Relay Activation mode [rLYS]
(H) High the relay energizes when the setpoint is exceeded. (L) Low the relay energizes below the setpoint. The setpoint is indicated from left to right SP, SP2, and SP3. buttons, adjust the reading on the display to the desired
and
) Using the
relay settings: [LLL-], [LHL-], [LLH-], [HHH-].
If only 2 relays installed [LH] [HL] [HH] [LL].
2) Press the P button.
The meter exits the setpoint mode and returns to the operational display.
The Setpoint Relay programming mode is now complete.
Page 6
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
BL-40PSF DS (BL5)
BL-40PSF Functional Diagram
with analog output and two 5 Amp Form A relays
This meter comes standard with screw terminal plug connections.
This meter uses plug-in type screw terminal connectors for all input and output connections. The power supply connections (pins 4 and 5) have a unique plug and socket outline to prevent cross connection. The main board uses standard right-angled connectors.
Input Signal Pins 1 to 6 Pins to 6 are reserved for the input signal conditioner. See the data sheet for the selected input signal conditioner.
BL-40PSF DS (BL5)
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
Page 7
Auto sensing AC/DC power supply. For voltages between 85-265 VAC or 95-370 VDC (PS).
Pin 14 & Pin 15 - AC/DC Power Input: These pins are the power pins of the meter and they only accept a special polarized screw terminal plug that can not be inserted into any other input socket. The standard meter has a auto sensing AC/DC power supply that operates from 85-
265 VAC/95-370 VDC (PS Std). An optional isolated low voltage power supply that operates from 5-48 VAC/0-72 VDC (PS2) is also available.
Internal header pins 1, 2, 3, 6, and 7 are for factory settings only. Not for external use!
4 HOLD. By connecting the HOLD pin to the GND pin, the displayed reading is frozen, however, A/D conversions continue.
When the HOLD pin is disconnected from the GND pin, the correct reading is displayed.
5 GND. This pin is connected to the internal power supply ground.
+5V
VPP
HOLD
SDA
SCL
Page 8
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
BL-40PSF DS (BL5)
BL-40PSF DS (BL5)
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
Page 9
I-Series Input Signal Conditioning Modules Many additional input modules are available and others are constantly being developed. Check with your local distributor or www.texmate. com for updated information.
Pre-calibrated I-Series input modules, that have span or zero potentiometers, can be interchanged between any I-Series compatible meter, without recalibration, because all of the analog scaling and reference circuitry is self-contained within the module. Where appropriate, all the standard ranges shown are designed to be header selectable by the user, and Texmate's unique SPAN ADJUST Header facilitates scaling to almost any required engineering unit. See Input Module Component Glossary and Calibration on pages 3 and 4. Also see Two Point Digital Calibration and Digital Calibration on page 4.
Unless otherwise specified Texmate will ship all modules pre-calibrated with factory preselected ranges and/or scalings as shown in BOLD type. Other pre-calibrated standard ranges or custom ranges may be ordered. Factory installed custom scaling and other custom options are also available (see Ordering Information, Special Options on last page).
Symbols Indicate Module Compatibility Within Meter Families
IA06: AC Volts True RMS, 300/600V AC
ALL MODELS
SOME MODELS MODEL SPECIFIC
IA01: AC Volts Scaled RMS, 200/600V AC
IA07: AC Volts True RMS, 200mV/2V/20V AC
IA02: AC Volts Scaled RMS, 200mV/2V/20V AC
IA08: AC Milliamps True RMS, 2/20/200mA AC
IA03: AC Milliamps Scaled RMS, 2/20/200mA AC
IA04: AC Amps Scaled RMS, 1 Amp AC IA05: AC Amps Scaled RMS, 5 Amp AC
Fully User Scalable
IA09: AC Amps True RMS, 1 Amp AC IA11: AC Amps True RMS, 5 Amp AC
IA10: AC Millivolts, Scaled RMS, 100mV AC
Fully User Scalable
Page 0
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
BL-40PSF DS (BL5)
I-Series Input Signal Conditioning Modules IA12: AC Millivolt RMS Sigma Delta
ID07: DC Milliamps, 2/20/200mA DC with Offset and 24V Exc
ID01: DC Volts, 2/20/200V/Custom w/24V DC Exc
IF02: Line Frequency
ID02: DC Millivolts, 20/50/100/200mV DC w/24V DC Exc
IGYZ: Universal Direct Pressure (Absolute or Differential/Gage)
See below for ordering code options
ID03: DC Milliamps, 2/20/200mA DC w/24V DC Exc
ID04: DC Amps, 5A DC ID09: DC Amps, 1A DC
IP01: Process Loop, 4-20mA IP02: Process Loop, 4-20mA with 24VDC EXC 091E
Fully User Scalable
Fully User Scalable
ID05: DC Volts 2/20/200/Custom V DC with Offset and 24V Exc.
IP03: Process Input, 1-5V DC with Offset, 24V Exc
Fully User Scalable
BL-40PSF DS (BL5)
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
Page
IP07: Universal Process Input 2V/5V/10V/20V/200V/2mA/20mA/Custom
224C
IS05: Pressure/Load Cell 20/2mV/V, 5/10V Exc 4-wire
IPT1: Prototype Board for Custom Design
IS06: Pressure/Load Cell Ext Exc., 20/2mV/V, 4-wire
IR02: 3 wire Potentiometer 1K min (0-F.S.)
IS07: Pressure/Load Cell Ext Exc. High Impedance,
IT03: RTD, 100 Pt. 2/3/4-wire (-200 to 800C) IT04: RTD, 100 Pt. 2/3/4-wire (-200 to 1470F) IT05: RTD, 100 Pt. 2/3/4-wire (-199.9 to 199.9F) IT14: RTD, 100 Pt. 2/3/4-wire (-199.9 to 199.9C) 187C
IT06: Thermocouple, J Type (0-1400 F) IT08: Thermocouple, J Type (0-760 C)
IR03: Linear Potentiometer 1K min
IR04: Resistance 2K (Lynx only) IR05: Resistance 2K (Leopard only)
IS01: Strain Gage 5/10VDC Exc., 20/2mV/V, 4/6-wire IS02: Pressure/Load Cell
5/10VDC Exc., 20/2mV/V, 4/6-wire
IS04: Pressure/Load Cell Ext Exc., 20/2mV/V, 4/6=wire
IT07: Thermocouple, K Type (0-1999 F) IT09: Thermocouple, K Type (0-1260 C)
For higher accuracy digitally linearized RTD (P385 or P392) and Thermocouples (J/K/R and T), see the special Leopard Temperature meters DL-40H(/8 DIN) and BL-40H(/6 DIN) which use only two special thermocouple modules which are not compatible with regular Leopard Family meters.
IT-10
User Selectable Accuracy 0.05% + 2 digits.
IT-11
User Selectable Accuracy 0.05% + 2 digits.
RTD 00 Pt, 3/4 wire, C/F, /0. resolution
Page 2
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
BL-40PSF DS (BL5)
Input and Output Pins On most modules Pin is the Signal High input and Pin 3 is the Signal Low input. Typically Pin 2 is used for Excitation Voltage output.
24V DC Output Header On some modules this header enables a 24V DC 25mA (max) Excitation/Auxiliary output to be connected to Pin 2.
INPUT RANGE Header
Range values are marked on the PCB. Typically two to four positions are provided, which are selected with either a single or multiple jumper clip. When provided, a custom range position is only functional when the option has been factory installed.
SPAN Potentiometer (Pot)
If provided, the 5 turn SPAN pot is always on the right side (as viewed from the rear of the meter).
Typical adjustment is 20% of the input signal range.
SPAN ADJUST Header
This unique five-position header expands the adjustment range of the SPAN pot into five equal 20% steps, across 00% of the input Signal Span. Any input Signal Span can then be precisely scaled down to provide any required Digital Display span from 999 counts to 00 (one count).
SPAN RANGE Header
When this header is provided it works in conjunction with the SPAN ADJUST Header by splitting its adjustment range into a Hi and a Lo range. This has the effect of dividing the adjustment range of the SPAN pot into ten equal 0% steps across 00% of the input Signal Span.
ZERO Potentiometer (Pot)
If provided, the ZERO pot is always to the left of the SPAN pot (as viewed from the rear of the meter). Typically it enables the input signal to be offset 5% of full scale (-00 to +00 counts).
ZERO OFFSET RANGE Header When provided, this three position header increases the ZERO pots capability to offset the input signal, to 25% of the digital display span.
For example a Negative offset enables a to 5V input to display 0 to full scale. The user can select negative offset, positive offset, or no offset (ZERO pot disabled for two step non-interactive span and offset calibration).
When this header is provided, it works in conjunction with the ZERO OFFSET RANGE Header, and expands the ZERO pots offset capability into five equal negative steps or five equal positive steps. This enables virtually any degree of input signal offset required to display any desired engineering unit of measure.
In addition to the analog calibration capabilities that enable many modules to be interchanged between different meters without loss of accuracy the Leopard Family of meters have enhanced Digital Calibration functions. See Page 4
Basic standard range calibration of direct reading modules that utilize either Auto Zero or a ZERO pot, an INPUT RANGE Header and or a SPAN pot.
If the module has an INPUT RANGE Header, reposition the
jumper clip to select the desired input signal range.
2. Apply a zero input or short the input pins. The display will auto zero, or if the module has a ZERO pot, it should be adjusted until the display reads zero.
3 Apply a known input signal that is at least 20% of the full scale input range and adjust the SPAN pot until the display reads the exact input value. For negative inputs, Leopard Family Meters will display negative overrange at 50% of full scale range.
4 Decimal Points. The selection or positioning of decimal points
has no effect on the calibration of the modules
Wide range scaling, in engineering units not requiring offsets, with modules that utilize auto-zero or a ZERO pot, a SPAN RANGE Header and or a SPAN ADJUST Header.
Texmates unique SPAN ADJUST and SPAN RANGE Headers provide the circuit equivalent of an ultra-precision one megohm 75 or 50 turn potentiometer that can infinitely scale down any Input Signal SPAN to provide any full scale Digital Display Span from 999 (counts) to 00 (one count).
If the module has an INPUT RANGE Header, and the required full
BL-40PSF DS (BL5)
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
Page 3
scale Digital Display Span (counts) is to be larger than the directly measured value of the input Signal Span, then the next lower range on the INPUT RANGE Header should be selected. The resulting over range Signal Span is then scaled down, by selecting the position of the SPAN RANGE Header and or the SPAN ADJUST Header, which will reduce the input Signal Span to a percentage, that the required Digital Display Span can be reached by calibration with the SPAN pot.
Example A: 0 to 0 V to read 0 to 800 gallons.
Signal Span = 0V, Digital Display Span = 800 counts
Select the 2 V INPUT RANGE Header position. This will provide a digital display of 800 counts with an input of only .8 V which is (.80)=8% of the examples 0 V Signal Span.
2 To scale down the Signal Span to 8% select the 20% Signal Span position on the SPAN ADJUST Header (position ) or if the module has a SPAN RANGE Header, select (LO Range) and 20% Signal Span position on the SPAN ADJUST Header (position 2).
3 Apply a zero input or short the input pins. The display will auto zero, or if the module has a ZERO pot, it should be adjusted until the display reads zero.
4 Apply 0 V and adjust the SPAN pot until the display reads
800.
Large offset scaling and calibration of process signal inputs with modules that utilize ZERO ADJUST Headers and or ZERO OFFSET RANGE Headers.
Texmates unique ZERO OFFSET RANGE Header enables the use of a simple two step scaling and calibration procedure for those process signals that require large offsets. This eliminates the back and forth interaction, between zero and span settings, that is often required to calibrate less finely engineered products.
The first step is to set the ZERO OFFSET RANGE Header to the center position (No Offset) and scale down the Input Signal Span to a percentage that will enable calibration with the SPAN pot to reach the required Digital Display Span.
The second step is to set the ZERO ADJUST and or ZERO OFFSET RANGE Header to provide a positive or negative offset of sufficient counts that calibration with the ZERO pot will offset the Digital Display Span to produce the required digital reading.
Example B: to 5 V to read 00 to 500 C.
Signal Span = 4V, Digital Display Span = 600 counts
If the module has an INPUT RANGE Header the 2 V position should be selected. This will provide a digital display of 600 counts for an input of .6 V which is (.6 4) = 40% of the examples 4 V signal span. To scale down the Signal Span to 40% select the 40% Signal Span position on the SPAN ADJUST Header (position 2).
2 If the module is a Process Input -5 V DC type, select the (Hi Range) position on the SPAN RANGE Header and the 00% Signal Span position on the SPAN ADJUST Header (position 5, max increase).
This will provide a digital display of 600 counts for an input of 4V which is 00% of the examples 4V Signal Span.
3 Set the ZERO OFFSET RANGE Header to the center position (no offset). Apply V and adjust the SPAN pot until the display reads 400. A 4V input would then read 600 counts.
4 Set the ZERO OFFSET RANGE Header to the negative offset position. If the module has a ZERO ADJUST Header select the position that will provide a negative offset of 500 counts.
Apply V and adjust the ZERO pot until the display reads 00. Apply 5 V and check that the display reads 500.
Example C: 4 to 20 mA to read 00.0 to +00.0% Signal Span = 6 mA, Digital Display Span = 000 counts.
The full scale Signal Span of the Process Input 4-20 mA modules is 0 to 20 mA for a full scale Digital Display Span of 0 to 2000 counts. This will provide a digital display of 000 counts with an input of only 0 mA which is (06)=62.5% of the examples 6 mA signal span.
2 To scale down the Signal Span to 62.5% select the (Hi Range) Position on the Span Range Header and the 70% Signal Span position on the SPAN ADJUST Header (position 2).
3 Set the ZERO OFFSET RANGE Header to the center position (no offset). Apply 4 mA and adjust the SPAN pot until the display reads 250. A 6 mA input would then read 000 counts.
4 Set the ZERO OFFSET RANGE Header to the positive offset position. If the module has a ZERO ADJUST Header select the position that will provide a negative offset of 250 counts.
Apply 4 mA and adjust the ZERO pot until the display reads 000.
Apply 20 mA and check that the display reads 000. Select decimal point XXXX to display 00.0 to 00.0.
Page 4
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
BL-40PSF DS (BL5)
the Leader in Measurement and Control Instrumentation
NEW!
LEOPARD FAMILY FEATURES
Smart 4 digit meters, tricolor and mono-color bargraphs
Front-panel digital scaling, offset, and setpoints
Bargraph can be independently scaled to a sensitivity of 100 counts full scale
within any portion of the digital scale
Over 38 different I-Series Input Signal Conditioners. For more info, please refer to
the I-Series Input Signal Conditioning Modules catalog.
24 V DC excitation is available to power external 4-20 mA transmitters and 5 or
10 V DC excitation is available for resistance bridge type sensors
Dual 10 & 5-amp relays, 4 relays total plus 16-bit analog output
1/16 DIN meters have one 10 Amp relay or two 5 Amp relays plus 16-bit analog
output or an extra 5 Amp relay
Auto-sensing AC/DC, wide range power supplies, 85-265 V AC / 95-370 V DC or
18-36 V AC / 9-60 V DC
Quick, easy mounting into any panel thickness
Direct flush mount into mosaic panels
Optional NEMA 4X membrane touch screen face plates
Optional NEMA 4X, IP65 clear polycarbonate lens covers
Optional metal surround case for DL and FL meters.
Standard plug-in screw terminal connectors are provided
NEW!
BL-404
5DL-40
BL-40PSF DS (BL5)
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
Page 5
BASIC MODEL #
DISPLAY
POWER SUPPLY
INPUT MODULES
ANALOG OUTPUT
RELAY OUTPUT
OPTIONS / ACCESSORIES
Add to the basic model number the order code suffix for each standard option required. The last suffix is to indicate how many different special options and or accessories that you may require to be included with this product.
Ordering Example: BL-40PSF-DR-PS1-IA01-0IC-R1-OA2, the 2 OAs are, CR-CHANGE and a 75-DMT96X24
basic model number
BL-40PSF.....96x24mm,.Leopard,.4.Digit,.Programmable.Scale.Factor
standard options for this model number
Order Code Suffix
Description
display
DR.... Red.LED,.0.56.inch.high DB...... Superbright Red LED, 0.56 inch high DG...... Green LED, 0.56 inch high
power supply
PS1.... 85.-.265VAC./.95.-.370VDC PS2..... 18 - 48VAC / 10 - 72VDC
input modules (partial list. see www.texmate.com)
Unless otherwise specified Texmate will ship all modules precalibrated with factory preselected ranges and/or scalings as shown in BOLD type.
IA01.... AC-Volts Scaled RMS, 200/600V AC IA02.... AC-Volts Scaled RMS, 200mV/2V/20V AC IA03.... AC-mA Scaled RMS, 2/20/200mA AC IA04.... AC-Amps Scaled RMS, 0-1.Amp.AC.(0-100.00) IA05.... AC-Amps Scaled RMS, 0-5.Amp.AC.(0-100.00) IA06.... AC-Volts True RMS, 200/600V AC IA07.... AC-Volts True RMS, 200mV/2V/20V AC IA08.... AC-mA True RMS, 2/20/200mA AC IA09.... AC-Amps True RMS, 0-1.Amp.AC.(0-100.00) IA10.... AC-Millivolt, Scaled RMS, 100mV.AC IA11.... AC-Amps True RMS, 0-5.Amp.AC.(0-100.00) IA12.... AC-Millivolt, True RMS, 100mV.AC ID01.... DC-Volts,.2/20/200V/Custom w/24V DC Exc ID02.... DC-Millivolt, 20/50/100/200mV DC w/24V DC Exc ID03.... DC-Milliamp, 2/20/200mA DC w/24V DC Exc ID04.... DC-Amps, 5A.DC ID05.... DC-Volts 2/20/200/Custom V DC w/Offset and 24V Exc ID07.... DC-Milliamp, 2/20/200mA DC w/Offset and 24V Exc ID09.... DC-Amps, 1A.DC IF02..... Line Frequency, 50-500VAC, 199.9Hz, or optional 400Hz IGYZ*... Universal Direct Pressure *View.the.IG-.Ordering.Code.on.page.11.to.determine.the.value.for.Y.&.Z.(IGAZ.to.IGKZ) IP01.... Process Loop, 4-20mA(0-100.00) IP02.... Process Loop, 4-20mA(0-100.00) w/24VDC Exc IP03.... Process Input, 1-5V.DC(0-100.00) w/Offset, 24V Exc IP07.... Universal Process 2V/5V/10V/20V/200V/2mA/20mA/Custom IPT1.... Prototype Board for Custom Design IR02.... 3-Wire Potentiometer 1K min (0-F.S.) IR03.... Linear Potentiometer, 3-wire, 1K min IR05.... Resistance 2K IS01.... Strain Gage 5/10VDC Exc., 20/2mV/V, 4/6-wire IS02.... Pressure 5/10VDC Exc., 20/2mV/V, 4/6-wire IS04.... Pressure Ext Exc., 20/2mV/V, 4/6wire IS05.... Pressure/Load Cell 20/2mV/V, 5/10V Exc 4-wire IS06.... Pressure/Load Cell Ext Exc., 20/2mV/V, 4-wire
IS07.... Pressure 20/2mV/V with High Impedance and External Excitation IT03..... RTD, 100 Pt. 2/3/4-wire.(-200.to.800C) IT04..... RTD, 100 Pt. 2/3/4-wire (-200.to.1470F) IT05..... RTD, 100 Pt. 2/3/4-wire (-190.0.to.199.0F) IT06..... Thermocouple, J Type (0-1400.F) IT07..... Thermocouple, K Type (0-1999F) IT08..... Thermocouple, J Type (0-760.C) IT09..... Thermocouple, K Type (0-1260C) IT14..... RTD, 100 Pt. 2/3/4-wire (-199.0.to.199.0C)
analoG output*
OIC..... Isolated analog 4-20mA (with a Max. Two-5A Form A Relays) OIV..... Isolated analog 0-10VDC (with a Max. Two-5A Form A Relays) *Note: When either of the Analog Output options is installed, only the R1, R2 and R11 Relay Output options can be co-installed (see below).
relay output
R1...... Single 5A Form A Relay R2...... Dual 5A Form A Relays R3...... Three 5A Form A Relays; SP1 & SP2 common** R11..... Single 10A Form C Relay R16..... Single 10A Form C & Single 5A Form A Relays** **R3 & R16 cannot be co-installed with Analog Output options.
special options and accessories (oas)
Part Number
Description
special options (specify inputs or outputs & req. reading)
CR-CHANGE........Calibrated Range Change to another Standard Range CS-L/40...........Custom Scaling within any Stnd. or Custom Selectable Range CSR-L/40..........Custom Selectable Range Installation or Modification CSS-L/40..........Custom Special Scaling beyond the Standard Range COA-L/SINGLE......Custom Output - Special Scaling of Analog Output COR-L/RELAY.......Custom Output - Relays Installed in Non-Standard Locations CCP-L/SETUP.......NRC to Set-up Custom Configuration - Functions, Codes CCP-L/INSTL.......Factory Installation - Custom Configuration
accessories (specify serial # for custom artwork installation)
For product details visit www.texmate.com Local Distributor Address
Page 6
Texmate, Inc. Tel. (760) 598-9899 www.texmate.com
BL-40PSF DS (BL5)
Texmate is an American manufacturer of high durability industrial grade panel meters, bar graphs, and transducers. Texmate's meters are frequently equipped with relays and various signal outputs for industrial automation applications and are known for their extremely long service life.