DL-40JANUS

With or without an External Signal

Source for Rescaling

0.56" or optional 0.8 large display red or green LED

General Features

External transmitters or signal conditioners can be eliminated

by directly connecting of the sensor output to one of Texmate's

29 Plug-in Input Signal Conditioners that include:

AC Current

AC/DC Voltage

Load Cell

Resistance

*Temperature

4 to 20 mA *See models DL-40-RTD and DL-40-RTD for higher accuracy

Pressure

Process

Prototype

digitally linearized thermocouple and RTD

Optional isolated 14 bit analog output. User or factory scalable to 4 to 20 mA, 0 to 20 mA or 0 to 10 V across any desired digital span from one count to the full scale range of 1999 to 9999 (12000 counts).

Optional Isolated Modbus RTU RS-485 serial communication with selectable baud rate (9600, 19200), address and parity.

Auto-sensing AC/DC power supply. For voltages between 85-265 VAC / 95-300 VDC (PS1) or 15-48 VAC / 10-72 VDC (PS2).

24 V DC excitation is available to power external transmitters and 5 or 10 V DC excitation is available for resistance bridge type sensors such as Load Cells and Pressure Transducers.

Standard red or optional green or super bright red 4-digit LED

display with range from 1999 to 9999 (12000 counts).

Red or green 0.8 LED large display option

Four annunciator LEDs provide front panel alarm status

indication for up to four setpoints.

Up to optional six relays in combination of six, four or two 4 Amp Form A relays or two 9 Amp Form C with two or four 4 Amp Form A relays are available.

Automatic intelligent averaging smooths noisy signals, while

providing a fast display response to real input signal changes.

Three-button programming via the front panel

(UP, DOWN and PROGRAM buttons).

Software Features

Front panel selectable four-level brightness control for digital

display and setpoint LEDs.

Four programmable setpoints.

Relay activation can be selected to occur above (HI) or below

(LO) each setpoint.

Hysteresis setting for all four setpoints. Delay on make and

delay on break for SP1 and SP2.

Peak and Valley. View and Reset.

Program Lock switch

A powerful, smart, programmable panel meter with optional Modbus RS-485 serial, analog and up to six relays output for measurement and control applications in a 1/8 DIN 96x48mm case.

Specifications

Input Specs:................Depends on Input signal conditioner A/D Converter:.............14 bit single slope Accuracy:.....................(0.05% of reading + 2 counts) Temp. Coeff.:...............100 ppm/C (Typical) Warm up time:.............2 minutes Conversion Rate:.........5 conversions per second (Typical) Display:........................4 digit 0.56" Red LED display (std),

0.56 or 0.8" Red, Green or Super Bright Red (optional)

Range 1999 to 9999 counts.

Polarity:........................Assumed positive. Displays negative Decimal Selection:.......Front panel button selectable, XXXX Positive Overrange:.....Top segments of digital display flash Negative Overrange:...Bottom segments of digital display flash Relay Output:..............Up to Six Relays in combination of six, four or two 4 Amp Form A relays or two

9 Amp Form C with two or four 4 Amp Form A relays.

Analog Output:............Isolated 14 bit user scalable mA or V AIC (mA out)................ 4-20 mA @ 0 to 500 max loop resis-

tance.

AIV (volts out).............. 0-10 V DC @ 500 or higher resistance Power Supply:.............AC/DC Auto sensing wide range supply PS1 (std)..................... 85-265 VAC / 95-300 VDC, 50-400Hz @ 3W PS2..............................15-48 VAC / 10-72 VDC, 50-400Hz @ 2.5W Operating Temp.:.........0 to 60 C Storage Temp:.............20 C to 70 C.

Relative Humidity:.......95% (non condensing) Case Dimensions:.......1/8 DIN, Bezel: 96x48 mm (3.78x1.89) Depth behind bezel: 117 mm (4.61) Plus 11.8 mm (0.47) for Right-angled

connectors, or plus 20 mm (0.79) for Straight-thru connector.

Weight:........................6.5 oz., 8.5 oz when packed

Input Module Compatibility

LEOPARD FAMILY: More than 29 different Plug-in I-Series Input Signal Conditioners are approved for Texmates Leopard Family of meters.

Some examples are shown on pages 12 - 14.

See www.texmate.com for an up to date listing.

Index

Page 1

Controls and Indicators

SP4

SP3

SP2

SP1

PROGRAM

BUTTON

UP ARROW

BUTTON

DOWN ARROW

BUTTON

Glossary of Programming Symbols To explain software programming procedures, logic diagrams are used to visually assist in following the programming steps. The fol-lowing symbols are used to represent various functions and associated display elements of the meter:

Symbol

Explanation

This symbol

OPERATIONAL DISPLAY.

represents

the

This is the PROGRAM button.

This is the UP button.

This is the DOWN button.

When a button is shown, press and release it to go onto the next step in the direction indicated by the arrow. When two or more buttons are shown, each with an arrow, this indicates that there is a number of programming choices.

When two buttons are shown side by side and enclosed by a dotted line, they must be pressed at the same time then released to go onto the next programming step.

If the display is shown with XXXX it means the value displayed will be the previously set value. When a number is shown it indicates the initial factory default setting or a specific example number.

Page 2

Front Panel Buttons

Program Button

The

When pressed at the same time as the calibration mode. When pressed at the same time as the ton, it initiates the setpoint setting mode.

button is used to move from one program step to the next. button, it initiates the but-

Up Button

When in the operational display, pressing the allows you to view and reset the Peak and Valley Lowest Readings.)

button alone, (Highest and

When in the calibration mode or the setpoint setting mode the button is used to increase the value of the displayed parameter.

Down Button

When in the operational display, pressing the button alone, allows you to view, but not change, the setting of setpoint 1,2,3 & 4.

When in the calibration mode or the setpoint setting mode the button is used to decrease the value of the displayed parameter.

When two displays are shown together with

bursts, this indicates that the display is

toggling (flashing) between the name of the

function and the value.

[ScAL]

[9999]

Text or numbers shown between square

brackets in a procedure indicate the pro-

gramming code name of the function or the

value displayed on the meter display.

When the

and

buttons are shown

together, the display value can be increased

by pressing and releasing the

button

or decreased by pressing and releasing the

button.

When the

and

buttons are shown

with two displays, either display can be

selected by pressing and releasing the

buttons.

When there are more than two display selec-

tions they are shown in brackets below the

first display and are also selectable by press-

ing and releasing the

buttons.

A dotted box indicates these functions are

omitted or bypassed when the related hard-

ware is not present

The DL-40JANUS is an intelligent meter with a hierarchical software structure designed for easy programming and operation, as shown below in the software logic tree.

After the meter has been powered up, the four digits light up for three seconds and then settle to the operational display indicating the input signal.

Software Logic Tree

15 Second

Program Timeout

The meter has a 15 second program timeout. If no buttons are pressed for 15 seconds, at any stage of the programming sequence the meter will exit the programming mode and return to the operational display. Any program changes that were made prior to pressing the P button in the preceding step will not be saved.

Page 3

Manual Rescaling Mode

When the rear Auto/Manual switch is in the Manual position, the meter can be rescaled without applying an external signal by changing the oFSt (offset) and SCAL (scale) parameters in the user menu. A pre-calibrated Input Signal Conditioning module must be used. The meter assumes that this calibration used a true zero input (0V from conditioner to meter) resulting in a display value of 0 and a maximum input signal span (2V from conditioner to meter) resulting in a display value of the SCAL value set in the user menu. The linear equation is y = mx + b where m = (SCAL-0)/(2-0) and b = oFSt.

The default value of SCAL is 2000, but it may be set to any value between -1999 and +9999.

The internal Signal Span is limited to 3 V DC between1 V DC to+ 2 V DC. Any outputs from an Input Signal Conditioning module that exceed these limits will cause the meter to indicate overrange regardless of the Digital Display Span scaled. For example, an ID01 DC Volts Input Signal Conditioner can read +/-2VDC, but in the DL-40 will show under-range for a -1.2V input.

Manual Rescaling Procedure

STEP A Enter the Calibration Mode

1) Press the

Display toggles between [CAL] and [oFF].

buttons at the same time.

and

2) Press and hold the button.

Display changes from [oFF] to [on].

3) Press the P button. Display toggles between [CAL] and [out].

STEP B Select Between Calibration of Input or Output

Note: If the analog output option is not present, Step B is skipped and the program goes directly from Step A to Step C.

1) Press the

to [inPt].

button to select the display toggling from [CAL]

2) Press the

previous offset setting.

button. Display toggles between [oFSt] and the

STEP C Set the Offset on the Digital Display

1) Using the

desired offset. This is the reading that the meter will display for a

buttons, adjust the digital display to the

and

zero input.

2) Press the

previous Scale factor.

button. Display toggles between [SCAL] and the

STEP D Set the Scale factor on the Digital Display and

1) Using the

desired Scale factor. The default value is 2000, for which a 2V

buttons, adjust the meter display to the

input will read 2000. If the scale factor is changed the display will change proportionately. Therefore if the Scale factor is changed

to 1000 then for the same 2V input the display would read 1000.

2) Press the P button.

The Digital Calibration Procedure Mode is Now Complete.

The menu branches to the DECIMAL POINT AND BRIGHTNESS SE LECTION, (see page6) and the display flashes [dP] and the previous decimal point selection.

Page 4

Auto Calibration Mode

When the rear Auto/Manual switch is in the Auto position, the meter can be calibrated with an automatic scale factor calculation, by applying a low input signal (InLo), entering the desired low display reading for that signal (ZERO), then applying a high input signal (InHi), and then entering the desired high display reading (SPAN). The meter then automatically calculates and programs in the requisite scale factor using a true linear (y=mx + b) calculation where m = (SPAN-ZERO)/(InHi-InLo) and b = ZERO, but within the following parameters.

1. Positive and negative signals may be applied, but the difference between the high and the low signal inputs must be at least 1000 counts or Err will be indicated.

2. Positive and Negative values for the desired reading can be entered, but the scale factor created can not exceed the Digital Display Span capability of the meter which is 12,000 counts between 1999 to 9999.

3. The internal Signal Span is limited to 3 V DC between 1 V DC to + 2 V DC. Any outputs from an Input Signal Conditioning module that exceed these limits will cause the meter to indicate overrange regardless of the Digital Display Span scaled.

Note: Most input signal conditioners have provisions for analog calibration and scaling. If the meters digital scale factor is set to read zero with a zero input (shorted input), and to read 1000 with a 1.000 V input, any pre-calibrated signal conditioner with an output that does not exceed 1 V to + 2 V, will read correctly in the meter without any further calibration.

Auto Calibration Procedure

STEP A Enter the Calibration Mode

buttons at the same time.

and

1) Press the

Display toggles between [CAL] and [oFF].

2) Press and hold the button.

Display changes from [oFF] to [on].

3) Press the

previous zero setting.

button. Display toggles between [ZErO] and the

STEP B Select Between Two Point Digital Calibration of Input Signal and

Two Point Analog Output

Note: If the analog output option is not present, Step B is skipped and the program goes directly from Step A to Step C.

1) Press the

button to select the display toggling from [CAL]

to [inPt] input calibration.

2) Press the

previous zero setting.

button. Display toggles between [ZErO] and the

STEP C Set the Meters Low Input Signal Reading on the Digital Display

1) Apply a zero or low signal to the meter. (Positive or negative values are allowed)

buttons, adjust the meter display to the

and

2) Using the

desired reading for the applied low input signal.

3) Press the

previous span setting.

button. Display toggles between [SPAn] and the

STEP D Set the Meters High Input Signal Reading on the Digital Display

1) Apply a high input signal to the meter.

2) Using the

desired reading for the applied high input signal.

3) Press the P button.

and

buttons, adjust the digital display to the

The Digital Calibration Procedure Mode is Now Complete.

If the digital calibration was successfully completed, the menu branches to the DISPLAY FUNCTION CONFIGURATION MODE, (see page 7) and the display flashes [dP] and the previous setting.

ERROR

Indicates Unsuccessful Calibration

If the calibration was unsuccessful, the display indicates [Err], the new calibration settings just entered will not take effect and the previously stored setting will remain.

The three most likely causes of an error during calibration are:

1) The full scale and zero signals were too similar. The full scale signal must be at least 1000 counts greater than the zero or low input signal (positive and negative values are allowed).

2) The scaling requirement exceeded the capability of the meter

(1999 to 9999).

3) No input signal present, or incorrect connections.

Page 5

Two Point Analog Output Range Setting and Calibration

STEP A Enter the Calibration Mode

and

buttons at the same time.

1) Press the

Display toggles between [CAL] and [oFF].

2) Press the

3) Press the P button. Display toggles between [CAL] and [out] input calibration.

button. Display changes from [oFF] to [on].

Note: If at this point the display skips directly to toggle between [oFSt] (Manual) or [ZErO]

(Auto) and the previous setting, the software is detecting that the optional analog output hardware is NOT installed.

STEP B Enter the Analog [oUT] Output Mode

1) Press the P button. Display toggles between [CLo] and an internal scale factor.

STEP C Set or Calibrate the [CLo] Low Analog Output Range

1) Select the voltage or current loop output header position on the output module. (See Component Layout on page 9).

2) Connect a multimeter to pins 16 and 17 on the output module. (See Rear Panel Pinouts on page 8). Using the

buttons, adjust the analog

and

output to the desired low value as shown on the multimeter display. cLo may be adjusted to any value from 0.3 mA to 17 mA (mA output selected) or from 0.6 V to 8 V (volt output selected)

3) Press the P button. Display toggles between [CHi] and an internal scale factor.

STEP D Set or Calibrate the [CHi] High Analog Output Range

1) Using the

and

buttons, adjust the analog output to the desired high value as shown on the multimeter display. CHi may be adjusted to any value from 17 mA to 21 mA (mA output selected) or from 8 V to 10.3 V (volt out

put selected)

2) Press the

button. The display exits the calibration mode and returns to

the operational display.

Note: Having established the Low and High range of the analog output, the digital span can now be selected which will set the two digital points between which the analog output will occur. (See Digital Span Selection below).

Decimal Point and Brightness Selection

STEP A Enter the Decimal Point and Brightness Mode Through the Sub Menu

[CAL] [oFF]

1) Press the

Display toggles between [CAL] and [oFF].

2) Press the P button. Display shows previous [dP] selection.

buttons at the same time.

and

STEP E Set the Decimal Point, adjust the display to the desired decimal point setting. 1) Using the 2) Press the P button. Display toggles between [br] and the previous [br] setting.

and

STEP F Set the Display Brightness

1) Using the

and

buttons, adjust the display to the desired brightness

setting (4 is the brightest setting).

2) Press the

button. Display brightness changes to new setting and display

toggles between [AnHi] and the previous [AnHi] setting.

Digital Span Selection for Analog Range Output

STEP G Setting the Digital Span Point for Analog High Output

buttons, adjust the display to the desired digital value 1) Using the which sets the point at which the selected analog high output range will occur.

2) Press the P button. Display toggles between [AnLo] and previous [AnLo] setting.

and

STEP H Setting the Digital Span Point for Analog Low Output

buttons, adjust the display to the desired digital value 1) Using the which sets the point at which the selected analog low output range will occur.

2) Press the

button. The display exits the calibration mode and returns to

and

the operational display.

Note: Any two digital scale points from 1999 to 9999 can be selected. The digital scale points for analog high and analog low can be reversed for reversed 20-4 mA output. The span of the digital scale can be as small as two counts however small spans cause the 16 bit D to A to increment in stair case steps.

Page 6

Modbus RTU & RS-485 Communication Settings

The Modbus/RS-485 communication settings sub-menu allows you to set the following parameters:

a) Baud Rate this is the baud rate of the RS-485 serial communication between the meter (slave) and Modbus master. Options are

9600 (default, meter shows 96) and 19200 (meter shows 192).

b) Address this is the meters Modbus address on the RS-485 loop. Typically, RS-485 limits the number of devices on the loop to 32, but the DL-40 supports the full Modbus address range of 1-247.

Address 1 is the default value.

c) Parity this is the parity setting for the RS-485 serial communication between the meter (slave) and Modbus master. Options are: None (display shows 0; Odd (display shows 1); Even (default, display shows 2).

The meters response time to a read command from the master is 40-45msec (typically 42msec). The response time for a write command is 70-75msec (typically 72msec). This is due to the module having to communicate to the meters core firmware to complete the desired command. Exception responses are handled directly by the module and typically have a response time of 3msec.

Modbus RTU Implementation

The DL-40 Modbus communication module supports the following

Modbus commands:

a) Read Holding Register (0x03)

b) Write Single Register (0x06)

Modbus addresses for DL-40JANUS registers are shown on

the next page

The following are some things to note about particular registers:

a) Modicon address 40001 RELAY has the bit values for Sp3 & Sp4 and LED3 & LED4 reversed. There is an historical reason for this, and we have chosen to maintain backward compatibility in case customers want to send their meters in for a Modbus upgrade (at a nominal fee).

b) Modicon addresses 40002 INP, 40026 PEAK, 40027 VALY,

40029 ZERO, 40029 SPAN return a 2 byte hexadecimal value of the meters display (in counts) and does not include the decimal point. If you need the decimal value with decimal point, you will need to read the register, convert it to decimal, read 40024 (see below) to determine decimal location, then combine the two. Display counts are in Twos Complement notation.

a. Hex values for 0 to 9999 are 0x0000 to 0x270F.

b. Hex values for -1 to -1999 are 0xFFFF to 0xF831.

c. Over-range is indicated by a returned value of 9999 (0x270F).

d. Under-range is indicated by a returned value of -1999 (0xF831).

c) In order for Sp3 and Sp4 set point settings to work, the DL-40 must have the optional Output Carrier Board installed (P/N SA-DL/OM-CB).

d) All Delay on Make (DoM), Delay on Break (DoB) and Hysteresis

values are in units of whole seconds.

e) Modicon address 40023 RLYMOD uses the following values to set the relay activation mode (letter sequence is SP1, SP2, SP3, SP4):

a. 0 for HHHH

b. 1 for HLHL

c. 2 for LHLH

d. 3 for LLLL

e. H means relay is energized if input is equal to or

exceeds setpoint; L means relay is energized if input

is less than setpoint.

f. Note that the meter will not show the last two letters if

the Output Carrier Board option is not installed.

f) Modicon address 40023 DP uses the following values to set the

display decimal point location:

a. 0 for XXXX (none)

b. 1 for XXXX.

c. 2 for XXX.X

d. 3 for XX.XX

e. 4 for X.XXX

g) Modicon address 40025 BRIGHT must be a value between 1

(most dim) to 4 (most bright).

h) Modicon addresses 40028 and 40029 will have different meanings depending on the Auto calibration or Manual rescaling operational selection (see Auto Calibration Mode or Manual Rescaling Mode above). These are explained in the register table below.

i) Modicon addresses 40030 IZERO and 40031 ISPAN return hexadecimal values related to the Auto Mode calibration of the meter. They do not necessarily match expected values due variations and tolerances in the measurement circuit components, e.g., calibrating with a value of zero volts for the ZERO value may return a value of 0xFFFE (-2). These registers have no meaning in Manual Rescaling Mode).

Page 7

Modbus Addresses for DL-40 Registers

Page 8

Setpoint Setting and Relay Configuration Mode

The following programming steps are required to enter the setpoint values and configure the relay functions in a meter with four relays using four setpoints. Generally if less than four relays are installed the software auto detects missing relays and deletes reference to them from the menu. In some cases setpoints without relays are operational for display only purposes.

STEP A Enter the Setpoint Mode

1) Press the

Display toggles between [SP1] and the previous [SP1] setting.

buttons at the same time.

and

STEP B Set Setpoint 1 (SP1) 1) Using the and 2) Press the P button. Display toggles between [doM] and the previous [doM] setting.

buttons, adjust the display to the desired SP1 value.

STEP C Set the SP1 Delay-on-Make (doM) Delay Time Setting

1) Using the

and

buttons, adjust the display to the desired [doM] value

(0 to 9999 seconds). The reading must continuously remain in an alarm condition

until this delay time has elapsed before the relay will make contact (energize).

2) Press the P button. Display toggles between [dob] and the previous [dob] setting.

STEP D Set the SP1 Delay-on-Break (dob) Delay Time Setting

1) Using the

and

buttons, adjust the display to the desired [dob] value (0 to 9999 seconds). The reading must continuously remain in an non-alarm condition until this delay time has elapsed before the relay will break contact (de-energize).

2) Press the P button. Display toggles between [HYSt] and the previous [HYSt] setting.

STEP E Set the Hysteresis Setting for Setpoint 1

1) Using the and buttons, adjust the display to the desired hysteresis [hYSt] value.

2) Press the button. Display toggles between [SP2] and the previous [SP2] setting.

NOTE: Half of the Hysteresis value selected is applied above and below the setpoint.

NOTE: Steps F, G, H and J have functionally the same procedure as steps B, C, D, and E shown above.

STEP F Set Setpoint 2 (SP2) STEP G Set the SP2 Delay-on-Make (doM) Delay Time Setting STEP H Set the SP2 Delay-on-Break (dob) Delay Time Setting STEP I Set the Hysteresis Setting for Setpoint 2

1) Using the

2) Press the P button. Display toggles between [SP3] and the previous [SP4] setting.

buttons, adjust the display to the desired hysteresis [HYSt] value.

and

STEP J Set Setpoint 3 (SP3) (No [doM] or [dob])

1) Using the

2) Press the P button. Display toggles between [HYSt] and the previous [HYSt] setting.

buttons, adjust the display to the desired SP3 value.

and

STEP K Set the Hysteresis Setting for Setpoint 3

1) Using the

2) Press the P button. Display toggles between [SP4] and the previous [SP4] setting.

buttons, adjust the display to the desired hysteresis [HYSt] value.

and

STEP L Set Setpoint 4 (SP4) (No [doM] or [dob])

1) Using the

2) Press the P button. Display toggles between [HYSt] and 0.

buttons, adjust the display to the desired SP4 value.

and

STEP M Set the Hysteresis Setting for Setpoint 4

1) Using the

2) Press the P button. Display toggles between [rLYS] and the previous relay setting.

buttons, adjust the display to the desired hysteresis [HYSt] value.

and

STEP N Set Relay Activation mode [rLYS]

(H) High the relay energizes when the setpoint is exceeded. (L) Low the relay energizes

below the setpoint. The setpoint is indicated from left to right SP1, SP2, SP3, SP4.

1) Using the

relay settings: [LLLL], [LHLH], [HLHL], [HHHH].

buttons, adjust the reading on the display to the desired

and

If only 2 relays installed [LH--], [HL--], [HH--], [LL--].

2) Press the

The meter exits the setpoint mode and returns to the operational display.

button.

The Setpoint Relay programming mode is now complete.

Page 9

Connector Pinouts Connector Pinouts

Pinout Diagram

The Rear View of the Meter diagram shows the meter with the relay configuration: dual 9 Amp Form C and dual 4 Amp Form A relays. An analog output module is also shown as installed.

The DL-40JANUS uses plug-in type screw terminal connectors for all input and output connections. The power supply connections (pins 14 and 15) have a unique plug and socket outline to prevent cross connection. The main board and input signal conditioner use right-angled connectors as standard. The output module uses straight-thru connectors as standard.

Pin 19

Pins 14 and 15 AC/DC Power Input

Auto-sensing AC/DC power supply. For voltages between 85-265 V AC/95-370 V DC (PS1) or 18-48 V AC/10-72 V DC (PS2).

Pin 14 AC/DC Neutral. Neutral power supply line.

Pin 15 AC/DC line. Live power supply line.

Analog and RS-485 Output Board Pins

Pins 16 and 17 Analog Output Pin 16 Positive (+) analog output.

Pin 17 Negative () analog output.

Pins 18 to 21 Rear Panel Function Pins

Pins 18 to 21 provide functions that can be implemented with an external switch. Their pin definitions are:

Pin 18

DIM. By connecting the display dim (DIM) pin to the COMMON pin, the display brightness setting is halved.

COMMON. To activate the LOCK or DIM functions from the rear of the meter, the respective pins have to be connected to the COMMON pin. This pin is connected to the internal power supply ground.

Switch 1

AUTO/MANUAL SCALING Mode. When switch 1 is set to ON position, the Manual Scaling is selected. When switch 1 is set to OFF, the Auto Scaling is selected, and this is the default position.

Switch 2

LOCK. By setting the LOCK pin to the ON

position, the meter's programmed

parameters can be viewed but not changed.

Auto-sensing AC/DC power supply. For voltages between 85-265 V AC / 95-370 V DC (PS1) or 18-48 V AC / 10-72 V DC (PS2).

Meter Assembly Component Layout

Relay

Module

Output

CarrierBoard

RS-485

or Analog

Output Module

Input Signal

Conditioner

Main

Board

Standard plug-in screw terminal connectors provided by Texmate:

Input Signal Pins 1 to 6

Pins 1 to 6 are reserved for the input signal conditioner.

See the data sheet for the selected input signal conditioner.

Pins 8 to 12 Relay Output Pins

Note: If relays for setpoints 1 & 2 are installed on the main board, and a relay output module is used that also has relays in the setpoints 1 & 2 positions, the duplicate relays will operate in unison.

Pin 8 SP1 NO.

Pin 9 SP1 NO.

Pin 10 SP2 NO.

Pin 11 SP2 NO.

Pin 12 NO CONNECTION.

4 Normally Open 5 Amp Form A.

4 Normally Open 5 Amp Form A.

Page 10

Connector Pinouts continued

On board Relay Pins 8 to 11 and Relay Output Module Pins 22 to 29

*Note: If relays for setpoints 1 & 2 (R2)

are installed on the main board, and a relay output module is used that also has relays in the setpoints 1 &

2 (OR14 or OR34), the duplicate relays will operate in unison.

Relay Modules with 4 Independent 400V 210mA DC only SSRs

Installation Guidelines

Installation

1. Install and wire meter per local applicable codes/regulations, the particular application, and good installation practices.

2. Install meter in a location that does not exceed the maximum operating temperature and that provides good air circulation.

3. Separate input/output leads from power lines to protect the meter from external noise. Input/output leads should be routed as far away as possible from contactors, control relays, transformers and other noisy components. Shielding cables for input/output leads is recommended with shield connection to earth ground near the meter preferred.

4. A circuit breaker or disconnect switch is required to disconnect power to the meter. The breaker/switch should be in close proximity to the meter and marked as the disconnecting device for the meter or meter circuit.

The circuit breaker or wall switch must be rated for the applied voltage (e.g., 120VAC or 240VAC) and current appropriate for the electrical application (e.g., 15A or 20A).

5. See Case Dimensions section for panel cutout information.

6. See Connector Pinouts section for wiring.

7. Use 28-12 AWG wiring, minimum 90 C (HH) temperature rating. Strip wire approximately 0.3 in. (7-8 mm).

8. Recommended torque on all terminal plug screws is 4.5 lb-in (0.51 N-m).

Page 11

I-Series Input Signal Conditioning Modules

Many additional input modules are available and others are constantly being developed. Check with your local distributor or www. texmate.com for updated information.

Pre-calibrated I-Series input modules, that have span or zero potentiometers, can be interchanged between any I-Series compatible meter, without recalibration, because all of the analog scaling and reference circuitry is self-contained within the module.

Where appropriate, all the standard ranges shown are designed to be header selectable by the user, and Texmate's unique

Symbols Indicate Module Compatibility Within Meter Families

SPAN ADJUST Header facilitates scaling to almost any required engineering unit. See Input Module Component Glossary and Calibration on pages 14 and 15. Also see Manual Rescaling on page 4 and Auto Calibration on page 5.

Unless otherwise specified Texmate will ship all modules pre-calibrated with factory preselected ranges and/or scalings as shown in BOLD type. Other pre-calibrated standard ranges or custom ranges may be ordered. Factory installed custom scaling and other custom options are also available (see Ordering Information, Special Options on last page).

ALL MODELS

SOME MODELS MODEL SPECIFIC

IA06: AC Volts True RMS, 300/600V AC

ID01: DC Volts, 2/20/200V/Custom w/24V DC Exc

IA07: AC Volts True RMS, 200mV/2V/20V AC

ID02: DC Millivolts, 20/50/100/200mV DC w/24V DC Exc

IA08: AC Milliamps True RMS, 2/20/200mA AC

ID03: DC Milliamps, 2/20/200mA DC w/24V DC Exc

IA09: AC Amps True RMS, 1 Amp AC IA11: AC Amps True RMS, 5 Amp AC

Page 12

ID04: DC Amps, 5A DC ID09: DC Amps, 1A DC

Fully User Scalable

I-Series Input Signal Conditioning Modules

ID05: DC Volts 2/20/200/Custom V DC with Offset and 24V Exc.

IP01: Process Loop, 4-20mA IP02: Process Loop, 4-20mA with 24VDC EXC 091E

Fully User Scalable

ID07: DC Milliamps, 2/20/200mA DC with Offset and 24V Exc

IP03: Process Input, 1-5V DC with Offset, 24V Exc

Fully User Scalable

IP07: Universal Process Input 2V/5V/10V/20V/200V/2mA/20mA/Custom

224C

IF02: Line Frequency

IGYZ: Universal Direct Pressure (Absolute or Differential/Gage)

See below for ordering code options

Direct Pressure (IGYX, IGYY & IGYZ) Ordering Code Options

IR02: 3 wire Potentiometer 1K min (0-F.S.)

IR03: Linear Potentiometer 1K min

IR04: Resistance 2K (Lynx only) IR05: Resistance 2K (Leopard only)

Page 13

I-Series Input Signal Conditioning Modules

IS01: Strain Gage 5/10VDC Exc., 20/2mV/V, 4/6-wire IS02: Pressure/Load Cell

5/10VDC Exc., 20/2mV/V, 4/6-wire

IS04: Pressure/Load Cell Ext Exc., 20/2mV/V, 4/6=wire

IT03: RTD, 100 Pt. 2/3/4-wire (-200 to 800C) IT04: RTD, 100 Pt. 2/3/4-wire (-200 to 1470F) IT05: RTD, 100 Pt. 2/3/4-wire (-199.9 to 199.9F) IT14: RTD, 100 Pt. 2/3/4-wire (-199.9 to 199.9C) 187C

IS05: Pressure/Load Cell 20/2mV/V, 5/10V Exc 4-wire

IS06: Pressure/Load Cell Ext Exc., 20/2mV/V, 4-wire

IT06: Thermocouple, J Type (0-1400 F) IT08: Thermocouple, J Type (0-760 C)

IT07: Thermocouple, K Type (0-1999 F) IT09: Thermocouple, K Type (0-1260 C)

For higher accuracy digitally linearized RTD (P385 or P392) and Thermocouples (J/K/R and T), see the special Leopard Temperature meters DL-40-RTD and DL-40-RTD which use only two special thermocouple modules which are not compatible with regular Leopard Family meters.

IT-10

IT-11

Thermocouple J/K/R/T, C/F, 1/0.1 resolution User Selectable Accuracy 0.05% + 2 digits.

RTD 100 Pt, 3/4 wire, C/F, 1/0.1 resolution User Selectable Accuracy 0.05% + 2 digits.

Input Module Component Glossary

Input and Output Pins On most modules Pin 1 is the Signal High input and Pin 3 is the Signal Low input. Typically Pin 2 is used for Excitation Voltage output.

INPUT RANGE Header

Range values are marked on the PCB. Typically two to four positions are provided, which are selected with either a single or multiple jumper clip. When provided, a custom range position is only functional when the option has been factory installed.

24V DC Output Header On some modules this header enables a 24V DC 25mA (max) Excitation/Auxiliary output to be connected to Pin 2.

SPAN Potentiometer (Pot)

If provided, the 15 turn SPAN pot is always on the right side (as viewed from the rear of the meter).

Typical adjustment is 20% of the input signal range.

Page 14

Input Module Component Glossary Continue

SPAN ADJUST Header

This unique five-position header expands the adjustment range of the SPAN pot into five equal 20% steps, across 100% of the input Signal Span. Any input Signal Span can then be precisely scaled down to provide any required Digital Display span from 1999 counts to 001 (one count).

ZERO OFFSET RANGE Header When provided, this three position header increases the ZERO pots capability to offset the input signal, to 25% of the digital display span.

For example a Negative offset enables a 1 to 5V input to display 0 to full scale. The user can select negative offset, positive offset, or no offset (ZERO pot disabled for two step non-interactive span and offset calibration).

SPAN RANGE Header

When this header is provided it works in conjunction with the SPAN ADJUST Header by splitting its adjustment range into a Hi and a Lo range. This has the effect of dividing the adjustment range of the SPAN pot into ten equal 10% steps across 100% of the input Signal Span.

ZERO Potentiometer (Pot)

If provided, the ZERO pot is always to the left of the SPAN pot (as viewed from the rear of the meter). Typically it enables the input signal to be offset 5% of full scale (-100 to +100 counts).

Input Module Calibration Examples IA06 AC-Volts True RMS, 200/600V AC

SPAN POT

INPUT RANGE HEADER

IA11 AC-Amps True RMS

SPAN ADJUST

HEADER

SPAN POT

SPAN RANGE

HEADER

ZERO ADJUST Header

When this header is provided, it works in conjunction with the ZERO OFFSET RANGE Header, and expands the ZERO pots offset capability into five equal negative steps or five equal positive steps. This enables virtually any degree of input signal offset required to display any desired engineering unit of measure.

Input Module Analog Calibration

In addition to the analog calibration capabilities that enable many modules to be interchanged between different meters without loss of accuracy the Leopard Family of meters have enhanced Digital Calibration functions. See Page 4-5.

Basic standard range calibration of direct reading modules that utilize either Auto Zero or a ZERO pot, an INPUT RANGE Header and or a SPAN pot.

1 If the module has an INPUT RANGE Header, reposition the

jumper clip to select the desired input signal range.

2. Apply a zero input or short the input pins. The display will auto zero, or if the module has a ZERO pot, it should be adjusted until the display reads zero.

3 Apply a known input signal that is at least 20% of the full scale input range and adjust the SPAN pot until the display reads the exact input value. For negative inputs, Leopard Family Meters will display negative overrange at 50% of full scale range.

4 Decimal Points. The selection or positioning of decimal points

has no effect on the calibration of the modules

Wide range scaling, in engineering units not requiring offsets, with modules that utilize auto-zero or a ZERO pot, a SPAN RANGE Header and or a SPAN ADJUST Header.

Texmates unique SPAN ADJUST and SPAN RANGE Headers provide the circuit equivalent of an ultra-precision one megohm 75 or 150 turn potentiometer that can infinitely scale down any Input Signal SPAN to provide any full scale Digital Display Span from

1999 (counts) to 001 (one count).

Page 15

Input Module Calibration Procedures Continued

If the module has an INPUT RANGE Header, and the required full scale Digital Display Span (counts) is to be larger than the directly measured value of the input Signal Span, then the next lower range on the INPUT RANGE Header should be selected. The resulting over range Signal Span is then scaled down, by selecting the position of the SPAN RANGE Header and or the SPAN ADJUST Header, which will reduce the input Signal Span to a percentage, that the required Digital Display Span can be reached by calibration with the SPAN pot.

Example A: 0 to 10 V to read 0 to 1800 gallons.

Signal Span = 10V, Digital Display Span = 1800 counts

1 Select the 2 V INPUT RANGE Header position. This will provide a digital display of 1800 counts with an input of only 1.8 V which is (1.810)=18% of the examples 10 V Signal Span.

2 To scale down the Signal Span to 18% select the 20% Signal Span position on the SPAN ADJUST Header (position 1) or if the module has a SPAN RANGE Header, select (LO Range) and 20% Signal Span position on the SPAN ADJUST Header (position 2).

3 Apply a zero input or short the input pins. The display will auto zero, or if the module has a ZERO pot, it should be adjusted until the display reads zero.

4 Apply 10 V and adjust the SPAN pot until the display reads 1800.

Large offset scaling and calibration of process signal inputs with modules that utilize ZERO ADJUST Headers and or ZERO OFFSET RANGE Headers.

Texmates unique ZERO OFFSET RANGE Header enables the use of a simple two step scaling and calibration procedure for those process signals that require large offsets. This eliminates the back and forth interaction, between zero and span settings, that is often required to calibrate less finely engineered products.

The first step is to set the ZERO OFFSET RANGE Header to the center position (No Offset) and scale down the Input Signal Span to a percentage that will enable calibration with the SPAN pot to reach the required Digital Display Span.

The second step is to set the ZERO ADJUST and or ZERO OFFSET RANGE Header to provide a positive or negative offset of sufficient counts that calibration with the ZERO pot will offset the Digital Display Span to produce the required digital reading.

Example B: 1 to 5 V to read 100 to 1500 C.

Signal Span = 4V, Digital Display Span = 1600 counts

1 If the module has an INPUT RANGE Header the 2 V position should be selected. This will provide a digital display of 1600 counts for an input of 1.6 V which is (1.6 4) = 40% of the examples 4 V signal span. To scale down the Signal Span to 40% select the 40% Signal Span position on the SPAN ADJUST Header (position 2).

2 If the module is a Process Input 1-5 V DC type, select the (Hi Range) position on the SPAN RANGE Header and the 100% Signal Span position on the SPAN ADJUST Header (position 5, max increase).

This will provide a digital display of 1600 counts for an input of 4V which is 100% of the examples 4V Signal Span.

3 Set the ZERO OFFSET RANGE Header to the center position (no offset). Apply 1 V and adjust the SPAN pot until the display reads 400. A 4V input would then read 1600 counts.

4 Set the ZERO OFFSET RANGE Header to the negative offset position. If the module has a ZERO ADJUST Header select the position that will provide a negative offset of 500 counts.

Apply 1 V and adjust the ZERO pot until the display reads 100. Apply 5 V and check that the display reads 1500.

Example C: 4 to 20 mA to read 00.0 to +100.0% Signal Span = 16 mA, Digital Display Span = 1000 counts.

1 The full scale Signal Span of the Process Input 4-20 mA modules is 0 to 20 mA for a full scale Digital Display Span of 0 to 2000 counts. This will provide a digital display of 1000 counts with an input of only 10 mA which is (1016)=62.5% of the examples 16 mA signal span.

2 To scale down the Signal Span to 62.5% select the (Hi Range) Position on the Span Range Header and the 70% Signal Span position on the SPAN ADJUST Header (position 2).

3 Set the ZERO OFFSET RANGE Header to the center position (no offset). Apply 4 mA and adjust the SPAN pot until the display reads 250. A 16 mA input would then read 1000 counts.

4 Set the ZERO OFFSET RANGE Header to the positive offset position. If the module has a ZERO ADJUST Header select the position that will provide a negative offset of 250 counts.

Apply 4 mA and adjust the ZERO pot until the display reads 000.

Apply 20 mA and check that the display reads 1000. Select decimal point XXXX to display 00.0 to 100.0.

Case Dimensions

Page 16

SIDE VIEW

Clear Lockable Water-proof Lens Cover OP-N4X/96X48

Clear Lockable NEMA 4X Dust and Splash Proof Cover PN: OP-N4/96x48

O-ring Gasket

Safety Catch

Cover

Removable

key-lock

The clear lockable cover is designed to be dust and water proof to NEMA-4X, IP65 standards. The assembly consists of a base and cover with a cam hinge and key-lock fastening mechanism. An O-ring, or neoprene gasket forms a seal between the base and the panel. The cam hinge prevents the cover from closing when opened until pushed closed. The cover has a tapered recess that, when closed, forms a seal with a tapered spigot on the base. A key-lock employs a cam locking device to force the spigot into the recess, ensuring seal integrity. A safety catch keeps the cover closed even when the key is removed, and the keyhole can be used to attach a safety seal clip, preventing unauthorized opening.

Metal Surround Case Option OP-MTL96X48

Part No.

OP-MTL96X48

Meter with Metal Surround Case

and screw-type mounting clips

assembled

Screw-type

Mounting Clip

Ground

Tab

Metal Surround Case

& Mounting Clips

The meters plastic case is made from fire retardant polycarbonate. A metal surround case can be ordered to enhance the meters fire retardant capabilities and also provide shielding against electromagnetic interference (EMI). The metal case slides over the polycarbonate case and is held firmly in place by spring-type non-return clips. The Metal Surround Case must be factory installed on the polycarbonate case and once installed, it cannot be removed in the field.

With the metal case in place, the meters standard ratchet-type mounting clips can not be used. Instead a pair of screw-type DIN standard mounting clips are provided, which clip into holes on the side of the metal case and tighten against the rear of the panel. A ground tab on the metal case enables the metal case to be easily connected to the panel ground.

Page 17

Ordering Information

BASIC MODEL #

DISPLAY

DL-40JANUS

POWER SUPPLY

INPUT MODULES

ANALOG OUTPUT*

RELAY OUTPUT*

OPTIONS / ACCESSORIES

OA____

Add to the basic model number the order code suffix for each standard option required. The last suffix is to indicate how many different special options and or accessories that you may require to be included with this product. Please see our website, www.texmate.com to configure a meter and see current pricing.

Page 18

About TexMate

Texmate is an American manufacturer of high durability industrial grade panel meters, bar graphs, and transducers. Texmate's meters are frequently equipped with relays and various signal outputs for industrial automation applications and are known for their extremely long service life.