LEOPARD FAMILY

General Features

External transmitters or signal conditioners can be eliminated

by direct connection of the sensor output to more than

40 Plug-in Input Signal Conditioners that include:

AC/DC Current

AC/DC Voltage

Load Cell

Pressure

Process

Prototype

Optional isolated 16 bit analog output. User or factory scalable to 4 to 20 mA, 0 to 20 mA or 0 to 10 V across any desired digital span from one count to the full scale range of 1999 to

9999 (12000 counts).

Resistance

Temperature

4 to 20 mA

A Programmable Tricolor (Red-Green-Orange) or mono color

(red or green), 101 segment high brightness bargraph. Vertical or optional horizontal format.

Red 4-digit LED display with a range of -1999 to 9999

(12000 counts). Optional green digital display.

Front panel LED annunciators provide indication of setpoint status.

Two 10 Amp Form C, and two 5 Amp Form A relays available

Auto-sensing AC/DC power supply. For voltages between

85-265 V AC / 95-370 V DC (PS1) or 18-48 V AC / 10-72 V DC (PS2).

24 V DC excitation is available to power external 4/20mA transmitters and 5 or 10 V DC excitation is available for resistance bridge type sensors.

Provision to connect an external programming lockout switch.

Provision for external DIM switch to reduce the brightest

display setting by 50%.

Optional NEMA-4 front cover.

Automatic intelligent averaging, smooths noisy signals while providing a fast display response to real level changes.

Software Features

The bargraph can display, full scale, any desired portion of the digital reading.

Bargraph center zero function.

Four programmable setpoints with adjustable Hysteresis.

Setpoint 1 has delay-on-make and delay-on-break plus a special pump on pump off mode that creates a

Hysteresis Band between

SP1 and SP2.

Relay activation can be

selected to occur above (hi) or below (Lo) each setpoint.

Digital display blanking.

Decimal point setting.

Four-level brightness control

accessed by the

and adjusted by the

button

button.

FL-B101D40PS

Leopard Bargraph Meter

101 Segment, 4 Digit 0.32 LEDs

in a 9/64 DIN CASE

This smart Tricolor or Mono-color digital bar-

graph with programmable scale factor

has four fully programmable set points for mon-

itoring, measurement, and control applications.

Input Module Compatibility

LEOPARD FAMILY: More than 38 different Plug-in I-Series Input Signal Conditioners are approved for Texmates Leopard Family of meters.

Some examples are shown on pages 13 - 15.

See www.texmate.com for an up to date listing.

LEOPARD

Specifications

Input Specs:..............Depends on Input signal conditioner A/D Converter:..........14 bit single slope Accuracy:..................(0.05% of reading + 2 counts) Temp. Coeff.:............100 ppm/C (Typical) Warm up time:..........2 minutes Conversion Rate:......10 conversions per second (Typical) Digital Display:..........4 digit 0.31" LED red (std), green (optn)

Range 1999 to 9999 counts.

Bargraph Display:....101 segment 4 red vertical (std),

green or tricolor (optn), horizontal (optn) Polarity:....................Assumed positive. Displays negative Decimal Selection:....Front panel button selectable, XXXX Positive Overrange:..Bargraph and top segments of digital display flash.

Negative Overrange: First segment of bargraph and bottom

Relay Output:............Two 5 Amp Form A relays and Two

segments of digital display flash.

10 Amp Form C relays.

Analog Output:........Isolated 16 bit user scalable mA or V

OIC (mA out)..........4-20 mA @ 0 to 500 max loop resistance OIV (volts out)..........0-10 V DC @ 500 or higher resistance Power Supply:..........AC/DC Auto sensing wide range supply PS1 (std)................85-265 VAC / 95-370 VDC @ 2.5W max 4.2W PS2........................18-48 VAC / 10-72 VDC @ 2.5W max 4.2W

Operating Temp.:......0 to 60C Storage Temp:..........20C to 70C Relative Humidity:....95% (non condensing) Case Dimensions:....9/64 DIN (Bezel 36Wx144Hmm)

Depth behind bezel (5.83") 148mm Plus (0.7) 18mm for connectors

Weight:......................9.5 oz., 12 oz when packed

Index

FL-B101D40PS DS (FL10)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 1

Controls and Indicators

Setpoints

indicated

by an ON

Segment

Setpoints

indicated

by an OFF

Segment

Seven Segment

LED Display

101 Segment

Bargraph

LED

Annunciators

for Setpoints

1-4

Button

PROGRAM

Button

DOWN

Button

Front Panel Buttons

Program Button

The

When pressed at the same time as the calibration mode.When pressed at the same time as the it initiates the setpoint setting mode.

button is used to move from one program step to the next. button, it initiates the button,

Programming Conventions

To explain software programming procedures, logic diagrams are used to visually assist in following the programming steps. The following symbols are used throughout the logic diagrams to represent the buttons and indicators on the meter:

This symbol represents the OPERATIONAL DISPLAY.

This is the PROGRAM button.

This is the UP button.

This is the DOWN button.

When a button is shown, press and release it to go onto the next step in the direction indicated by the arrow. When an alternative dotted line is shown, this indicates that an alternative logic branch will be followed when a particular option is present.

When two buttons are shown side by side and enclosed by a dotted line, they must be pressed at the same time then released to go onto the next programming step.

If an X appears through a digit, it means that any number displayed in that digit is not relevant to the function being explained.

Up Button

When in the operational display, pressing the to view the setting of the saved Peak and Valley Values.

button allows you

When setting a displayed parameter during programming, the button is used to increase the value of the displayed parameter.

Down Button

button allows you When in the operational display, pressing the to change the Brightness Level as well as to view the setting of the setpoints SP1, SP2, SP3 & SP4.

When setting a displayed parameter during programming, the button is used to decrease the value of the displayed parameter.

Front Panel LED Display Annunciator LEDs

The annunciator LEDs indicate the alarm status. They are labeled from bottom to top: SP1, SP2, SP3, SP4.

Digital LED Displays

The digital LED displays are used to display the meter input signal readings. They also display the programming settings during programming.

Setpoint Indication

The position of setpoints on the bargraph display are indicated by an ON or OFF segment dependent on the bargraph display being above or below the setpoint.

and

When the buttons are shown together, the display value can be increased button by pressing and releasing the or decreased by pressing and releasing the

button.

and

When the buttons are shown with two displays, either display can be or selected by pressing and releasing the

buttons.

When two displays are shown together with bursts, this indicates that the display is toggling (flashing) between the name of the function and the value.

[Span]

[10000]

Text or numbers shown between square brackets in a procedure indicate the programming code name of the function or the value displayed on the meter display.

When there are more than two display selections they are shown in brackets below the first display and are also selectable by pressing and releasing the

buttons.

A dotted line enclosing an entire logic diagram indicates that programming branch will appear only when a particular option is present.

Page 2

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

FL-B101D40PS DS (FL10)

Software Logic Tree

The FL-B101D40PS is an intelligent bargraph meter with a hierarchical software structure designed for easy programming and operation, as shown below in the software logic tree.

Software Version is Displayed on Power-up When power is applied, all segments of the bargraph and digital display light up for 3 seconds. The version number of the installed software is then displayed for 2 seconds, after which, the operational display indicates the input signal.

15 Second Program Timeout Except for ZERO and SPAN settings in the Two Point Digital Calibration Mode and the Analog Output Range Setting and Calibration Mode (cLo and chi), the meter has a 15 second program timeout. If no buttons are pressed for 15 seconds in any of the other programming sequences, the meter will exit the programming mode and return to the operational display. Any program changes that were made prior to pressing the button in the preceding step will not be saved.

FL-B101D40PS DS (FL10)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 3

Digital Rescaling

The FL-B10140PSF meter may be rescaled without applying an external signal by changing the Offset and Scale factor.

Offset is the reading that the meter will display for a zero input. The Offset may be set to any value from -1999 to +9999. The default value of the Offset is 000

Scale factor is the gain of the meter. The displayed reading is directly proportional to the Scale factor. The default value of the scale factor is 2000, but it may be set to any value between -1999 and +9999.

For an input of 2V a calibrated meter will read 2000 with the default Scale factor of 2000, 3000 with a Scale factor of 3000 and 500 with a Scale factor of 500

If a linear scale is represented by mx + b, then the Scale Factor corresponds to the slope m and the Offset corresponds to the intercept b

The internal Signal Span is limited to 3 V DC between 1 V DC to + 2 V DC. Outputs from an Input Signal Conditioning module that exceed these limits will cause the meter to indicate overrange.

Note: Most input signal conditioners have provisions for analog calibration and scaling. If the meters digital Scale Factor is set to

2000 and Offset set to 0000 then, any pre-calibrated signal conditioner with an output that does not exceed 1 V to + 2 V, will read correctly in the meter without any further calibration.

MAIN MENU

Operational Display

Digital Rescaling Procedure

STEP A Enter the Calibration Mode

and

1) Press the

gles between [CAL] and [oFF].

2) Press the

[on].

3) Press the

[out].

buttons at the same time. Display tog-

button. Display changes from [oFF] to

button. Display toggles between [CAL] and

Note: If at this point, the display skips directly to STEP C and toggles between [ScAL] and the previous [ScAL] setting, the software is detecting that the optional analog output hardware is NOT installed.

STEP B Select Two Point Digital Calibration of Input Signal

button to select CAL [iP] for input sig-

button. Display toggles between [oFFS] and

1) Press the

nal calibration.

2) Press the

the

previous offset setting.

STEP C Set the Offset on the Digital Display

and

buttons, adjust the digital display to 1) Using the the desired offset. This is the reading that the meter will display for a zero input 2) Press the

the previous Scale factor.

button. Display toggles between [ScAL] and

STEP D Set the Scale factor on the Digital Display

and

1) Using the buttons, adjust the meter display to the desired Scale factor. The default value is 2000, for which a 2V input will read 2000. If the scale factor is changed the display will change proportionately. Therefore if the Scale factor is changed to 1000 then for the same 2V input the display would read 1000.

3) Press the

button.

The Digital Rescaling is now complete.

If the Digital Rescaling was successfully completed, the menu branches to the Digital Span Selection for Bargraph Display (see page 6), and the display flashes [bhi] and the previous setting.

Sub-menu

MODE

STEP A Calibration

Mode

To Digital Span Selection for Bargraph Display

See Page 7

STEP B Calibration

Mode

To Two Point Analog Output Range Setting

and Calibration

See Page 8

DIGITAL

RESCALING MODE

STEP C Offset

STEP D Scale

Factor

To Digital Span Selection for Bargraph Display Page 6

Page 4

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

FL-B101D40PS DS (FL10)

Successive Digital Rescaling to get Progressively Better Accuracy

STEP A

STEP B

STEP C

Texmate Meter

300

Offset = 0

Scale = 2000

3.5mV

Texmate Meter

320

Offset = 20

Scale = 2000

3.5mV

Texmate Meter

1190

Offset = 20

Scale = 2000

13.5mV

Hopper contains some material whose EXACT weight is not known.

It is estimated to be 320 pounds.

When a Texmate meter is connected, it displays 300 instead of 320.

Change offset to +20 to correct the Texmate meter display to 320.

A known load of EXACTLY 1000 pounds is now added to the hopper.

Texmate meter displays 1190 instead of 1320.

STEP D

STEP E

STEP F

Texmate Meter

1320

Offset = 20

Scale = 2219

13.5mV

Texmate Meter

Offset = 20

Scale = 2219

0.5mV

Texmate Meter

Offset = -40

Scale = 2219

0.5mV

Change scale to 2219 to correct the Texmate meter display to 1320

New scale = 2000 x 1320 / 1190 = 2219

The meter is approximately calibrated. Approximate, not exact, because the weight in STEP B is not exactly known.

Later (maybe many days later) when the hopper is finally empty, it is seen that the meter does not read zero.

Change Offset to -40 to correct the Texmate meter display.

Display is now correct.

STEP G

STEP H

STEP I

Texmate Meter

970

Offset = -40

Scale = 2219

10.5mV

Texmate Meter

1000

Offset = -40

Scale = 2287

10.5mV

Texmate Meter

Offset = -40

Scale = 2287

5mV

If a known weight of 1000 pounds is now added, the Texmate meter displays 970 instead of 1000.

Change Scale to correct this display.

New Scale = 2219x1000 / 970

The next time the hopper is empty, it will read 0 correctly.

error = 30 pounds

=2287

FL-B101D40PS DS (FL10)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 5

Digital Span Selection For Bargraph Display

The bargraph can be set to display full scale (0-101 bars) any portion of the

digital reading from a minimum of 100 counts to a maximum of 12,000

Example of Setting the Digital Span of the Bargraph Display to be Different than the Digital Display Range

counts. This provides higher resolution bargraph indication for those appli-

cations where the normal operating input signal range is less than the

desired full scale display range of the digital display.

For Example:

If the full scale range of the meter has been set from -1999 to

9999 (0-12,000 counts), but the normal operating range of the

input signal is between 4000 & 6000. The bargraph high parame-

ter [bhi] can be set to 6000 and the bargraph low parameter [bLo]

can be set to 4000.

This means that although the meter could digitally display a signal

from -1999 to 9999 (0-12,000 counts), the bargraph display only

begins to function at a reading of 4000, and reaches full scale indi-

cation at a reading of 6000. Although the digital display will con-

tinue reading up to 9999 before indicating overrange, the bargraph

display will indicate its overrange by flashing for readings above

6000.

Bargraph does not light up for Input Signals up to 3999 counts

Bargraph lights up for Input Signals above 4000 counts

STEP A Enter the Calibration Sub Menu Mode

1) Press the

and

buttons at the same time. Display toggles

between [CAL] and [oFF].

2) Press the

button. Display toggles between [bhi] and the

previous setting.

STEP B Set the Digital Span of the Bargraph Display (See example above) buttons, adjust the display to the desired

1) Using the

and

high parameter reading, e.g. 6000 counts.

2) Press the

button. Display toggles between [bLo] and the

previous setting.

3) Using the

and

buttons, adjust the display to the desired

low parameter reading, e.g. 4000 counts.

4) Press the

button. Display changes from [4000] to [dP].

Decimal Point and Brightness Selection

STEP C Set the Decimal Point 1) Using the

and

buttons, adjust the display to the desired

decimal point setting.

2) Press the

button. Display toggles between [br] and the

previous brightness setting.

STEP D Set the Bargraph and Digital Display Brightness

1) Using the

and

buttons, adjust the display to the desired

brightness setting (4 is the brightest setting).

2) Press the

previous [Anhi] setting.

button. Display toggles between [Anhi] and the

Note: If at this point, the display skips directly to STEP G and toggles between [Cto] and [oFF], the software is detecting that the optional analog output hardware is NOT installed.

Page 6

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

FL-B101D40PS DS (FL10)

Digital Span Selection for Analog Range Output Digital Span Selection for Analog Range Output

STEP E Selecting the [Anhi] Digital Value for Analog High Output

1) Using the

and

buttons, adjust the display to the desired digital value at which the [chi] Calibrated Analog High output will occur. For digital readings outside the digital span selected, the analog output will linearly rise above the value set for chi, up to the maximum analog output capability. However, the analog output will not go lower than the calibrated value set for cLo (see below).

2) Press the

button. Display toggles between [AnLo] and previous

[AnLo] setting.

STEP F Selecting the [AnLo] Digital Value for Analog Low Output

1) Using the

and

buttons, adjust the display to the desired

digital value at which the [cLo] Calibrated Analog Low output will occur. For Digital readings outside the Digital Span selected, the analog output will not go lower than the calibrated value set for cLo. button. The display toggles between [cto] and

2) Press the

[oFF].

Note: Any two digital span points from 1999 to 9999 can be selected. The digital values for [Anhi] analog high and [AnLo] analog low can be reversed to provide a 20 to 4mA output. The digital span selected can be as small as two counts, when using the analog output to function as a Control or Alarm Driver. Small digital spans will cause the high resolution 16 bit D to A to increment digitally in stair case steps.

See Two Point Analog Output Range Setting and Calibration at the top of the next page.

Bargraph Center Point Display Mode Selection

Example of Using the Center Point Bargraph Display Mode with a Unipolar Input

If the meter's full scale range is set to 5000 counts, the midpoint would be

2500 counts. If a signal of 2500 counts is applied only one segment at the

2500 count mark will light up. If a signal of 4000 counts is applied the segments between the center segment (2500 counts) and the 4000 count mark light up.

If a signal of 1000 counts is applied, the segments between the center segment (2500 counts) and the 1000 count mark will light up.

Example of Using the Center Point Bargraph Display Mode with Bipolar Signal Inputs

The meter may also be calibrated to display symmetrical bipolar signals such as 1 V or 10 V. When the center point display mode is selected, it will then function as a center zero meter. When positive signals are applied, the bar will go up from the center point, and when negative signals are applied, the bar will go down from the center point.

STEP G Bargraph Center Point Mode Selection (See example above) 1) To select bargraph center point mode, press the

button. Display changes from [oFF] to [on].

button. Display toggles between [diSP] and [on]

2) Press the

or [oFF].

STEP H Digital Display ON/OFF Selection

1) To set the display to [oFF], press the toggles between [diSP] and [oFF].

button. Display

2) Press the

button. The display exits the calibration mode

and returns to the operational display. Only the bargraph display is on and the digital display is off.

If the digital display is selected to be off, pressing any button to make programming changes or to view setpoints activates the digital display.

When the procedure is complete, the digital display will then automatically switch off.

The Display/Bargraph settings are now complete.

FL-B101D40PS DS (FL10)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 7

1) Press the

and [oFF].

2) Press the

Press the

Two Point Analog Output Range Setting and Calibration Two Point Analog Output Range Setting and Calibration Determine if the Analog Output Selection Header is in the 4 to 20mA (0-20mA) position or the 0 to 10VDC position. If necessary, the module may have to be removed and the header position changed (see Component Layout below).

Note: Always disconnect power from the meter before removing the analog output module to adjust the mA or Volts output selection header and reinstalling it. When power is reconnected, the meters software will automatically detect the presence or absence of the analog output module.

STEP A Enter the Calibration Mode

and

buttons at the same time. Display toggles between [cAL]

button. Display changes from [oFF] to [on]. button. Display toggles between [cAL] and [out] input calibration.

Note: If at this point the display skips directly to toggle between Zero and the previous Zero setting, the software is detecting that the optional analog output hardware is NOT installed.

STEP B Enter the Two Point Analog [ouT] Output Range Setting and Calibration Mode button. Display toggles between [cLo] and an internal scale factor.

1) Press the

and

STEP E Set or Calibrate [cLo] the Low Analog Value of the Analog Output Range 1) Connect a multimeter to analog output pins 17 and 18 (see Rear Panel Pinouts on page 11). Using the buttons, adjust the analog output to the desired low value as measured on the multimeter. cLo may be adjusted to any value from 0.3 mA to 18 mA (mA output selected) or from 0.6 V to 8 V (volt output selected). However, the output of cLo must always be less than the value selected for chi. If a reversed analog output is desired, the values selected to establish the Digital Span can be reversed (see top of page 7). For digital readings outside the Digital Span selected, the analog output will not go any lower than the calibrated value set for cLo. However, the analog output will linearly rise above the value set for chi, up to the the maximum analog output capability (see chi below).

2) Press the

button. Display toggles between [chi] and an internal scale factor.

STEP F Set or Calibrate [chi] the High Analog Value of the Analog Output Range 1) Using the buttons, adjust the analog output to the desired high value as measured on the multimeter display. chi may be adjusted to any value from 18 mA to 24 mA (mA output) or from 8 V to 10.3 V (volt output).

However, the value must be higher than the value selected for cLo. For digital readings outside the Digital Span selected, the analog output will linearly rise above the value set for chi, up to the maximum analog output capability.

2) Press the button. The meter exits the calibration mode and returns to the operational display.

and

Note: The analog output range established by the values selected for cLo and chi will occur, automatically scaled, between the two digital values selected for AnHi and AnLo.

However, the analog output can linearly rise above the chi value set for digital readings outside the digital span selected. See Digital Span Selection on page 7.

Case Dimensions

PANEL CUTOUT

Page 8

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

FL-B101D40PS DS (FL10)

Setpoint Setting and Relay Configuration Mode

The following programming steps are required to enter the setpoint values and configure the relay functions in a meter with four relays using four setpoints. Generally if less than four relays are installed, the setpoints without relays are operational in software for tri-color control or display only purposes. To remove unwanted setpoint indications, set them to 9999 or -1999 depending on the relay activation mode selected.

STEP A Enter the Setpoint Mode

1) Press the

SP1 setting.

and

buttons at the same time. Display toggles between [SP1] and the previous

STEP B Set Setpoint 1 [SP1] and 1) Using the button. Display toggles between [doM] and the previous [doM] setting. 2) Press the

buttons, adjust the display to the desired SP1 value.

STEP C Set the SP1 Delay-on-Make [doM] Delay Time Setting

and

1) Using the buttons, adjust the display to the desired [doM] value (0 to 9999 seconds).

The reading must continuously remain in an alarm condition until this delay time has elapsed before the relay will make contact (energize).

2) Press the

button. Display toggles between [dob] and the previous [dob] setting.

STEP D Set the SP1 Delay-on-Break [dob] Delay Time Setting

and

1) Using the buttons, adjust the display to the desired [dob] value (0 to 9999 seconds).

The reading must continuously remain in a non-alarm condition until this delay time has elapsed before the relay will break contact (de-energize).

2) Press the

button. Display toggles between [hYSt] and the previous [hYSt] setting.

STEP E Select the Hysteresis [hYSt]

1) Using the

2) Press the

buttons, select the Hysteresis to be ON or OFF.

and

button. Display toggles between PUM and (on) or (oFF).

STEP F Select Pump [PUM] (on) or (oFF)

1) Using the buttons, select the Pump to be ON or OFF. When PUM is selected ON, and SP2 is set at a value higher than SP1, the SP1 relay will operate in a special "pump on pump off" mode.

SP2 acts as the upper limit and SP1 acts as the lower limit of the Hysteresis Band on the SP1 relay.

and

For filling applications:

[rLYS] should be set to [LhXX] (see step M). The SP1 relay and SP1 LED Annunciator will then activate for inputs less than the SP1 setpoint, and remain ON until the SP2 setpoint is reached.

For emptying applications:

[rLYS] should be set to [hhXX] (see step M). The SP1 relay and SP1 LED Annunciator will then activate for inputs greater than the SP2 setpoint, and remain ON until the SP1 setpoint is reached.

2) Press the

button. Display toggles between [SP2] and the previous SP2 setting.

STEP G Set Setpoint 2 (SP2) and 1) Using the button. Display toggles between [hySt] and the previous [hySt] setting. 2) Press the

buttons, adjust the display to the desired SP2 value.

STEP H Select the Hysteresis [hYSt]

1) Using the

2) Press the

buttons, select the Hysteresis to be ON or OFF.

and

button. Display toggles between [SP3] and the previous [SP3] setting.

STEP I

Set Setpoint 3 (SP3) (No [doM] or [dob]) 1) Using the

2) Press the

buttons, adjust the display to the desired SP3 value.

and

button. Display toggles between [hySt] and the previous [hySt] setting.

STEP J Select the Hysteresis [hYSt]

1) Using the

2) Press the

buttons, select the Hysteresis to be ON or OFF.

and

button. Display toggles between [SP4] and the previous [SP4] setting.

STEP K Set Setpoint 4 (SP4) (No [doM] or [dob])

1) Using the

2) Press the

buttons, adjust the display to the desired SP4 value.

and

button. Display toggles between [hySt] and the previous [hySt] setting.

STEP L Select the Hysteresis [hYSt]

1) Using the

2) Press the

buttons, select the Hysteresis to be ON or OFF.

and

button. Display toggles between [rLYS] and the previous relay setting.

Please Continue On Next Page.

FL-B101D40PS DS (FL10)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 9

Setpoint Setting and Relay Configuration Mode Continued

STEP M Set Relay Activation mode [rLYS] for SP1

(h) High the relay energizes when the setpoint is exceeded. (L) Low the relay energizes below the setpoint. The setpoint is indicated from left to right SP1, SP2, SP3, SP4.

1) Using the

2) Press the

and

button. The SP2 Relay Activation digit begins to flash, and its decimal point is lit.

buttons, select (L) or (h) for the first digit, which corresponds to SP1.

STEP N Set High (h) or Low (L) for SP2

1) Using the

2) Press the

and buttons, select (L) or (h) for the second digit, which corresponds to SP2. button. The SP3 Relay Activation digit begins to flash, and its decimal point is lit.

STEP O Set High (h) or Low (L) for SP3

1) Using the

2) Press the

and

button. The SP4 Relay Activation digit begins to flash, and its decimal point is lit.

buttons, select (L) or (h) for the third digit, which corresponds to SP3.

STEP P Set High (h) or Low (L) for SP4

1) Using the

2) Press the

and

button.

buttons, select (L) or (h) for the fourth digit, which corresponds to SP4.

If a mono-color red or green display is installed then the Setpoint Relay Programming Mode is now complete and the meter returns to the operational display.

If a tricolor bargraph display is installed then the Bargraph Color Programming Mode will be entered and display toggles between [CoL] and the previous setting. Color selection menu will be displayed.

Bargraph Color Programming Mode

To comply with the latest safety requirements, the tri-color bargraph is designed like a traffic light, to display either red, orange or green, but only one color at a time. When the bar reaches a selected color change point, the entire bar will change to the color designated for that zone. This eliminates any ambiguity as to the signal status, especially just after transitioning to a new zone.

First (Step Q) is to select the color to be displayed, when the bar is below*, whichever set point is set to the lowest position.

Second (Steps R, S, T, and U) is to select the color to be displayed when the bar is above each specific set point, regardless of the order or position to which the set points are set.

However, if two or more setpoints with differently specified colors are positioned at the same set point value, the color specified for the set point with the highest identifying number will be displayed. When set points are set to the same value, the SP4 color overrides the SP3 color, the SP3 color overrides the SP2 color, and the SP2 color overrides the SP1 color.

STEP Q Select Bargraph Color when the bar is BELOW* the Setpoint that is set to the lowest position

1) Using the

2) Press the

buttons, select the desired bargraph color [grn], [oran] or [red]

and

button. Display toggles between [CSP1] and the previous color setting.

STEP R Select Bargraph Color when the bar is ABOVE* SP1 Setpoint

1) Using the

2) Press the

buttons, select the desired bargraph color [grn], [oran] or [red]

and

button. Display toggles between [CSP2] and the previous color setting.

STEP S Select Bargraph Color when the bar is ABOVE* SP2 Setpoint

1) Using the

2) Press the

buttons, select the desired bargraph color [grn], [oran] or [red]

and

button. Display toggles between [CSP3] and the previous color setting.

STEP T Select Bargraph Color when the bar is ABOVE* SP3 Setpoint

1) Using the

2) Press the

buttons, select the desired bargraph color [grn], [oran] or [red]

and

button. Display toggles between [CSP4] and the previous color setting.

STEP U Select Bargraph Color when the bar is ABOVE* SP4 Setpoint

1) Using the

2) Press the

display.

and buttons, select the desired bargraph color [grn], [oran] or [red] button. The meter exits the setpoint mode and returns to the operational

The Bargraph Color programming mode is now complete.

*Note: For horizontal display formats BELOW* should be read as, to the left and ABOVE* should be read as, to the right.

Page 10

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

FL-B101D40PS DS (FL10)

Functional Diagram

Connector Pinouts

This meter uses plug-in type screw terminal connectors for all input and output connections. The power supply connections (pins 23 and 24) have a unique plug and socket outline to prevent cross connection. The main board uses standard right-angled connectors.

Replacement 2-, 3-, and 4-pin plug connectors are available (see Accessories on page 20).

Note: The sequence of setpoint outputs on meters shipped prior to 2002 was 1-2-3-4. The sequence is now 3-1-4-2, enabling delay on make

(dom) and delay on break (dob) to be used with both Form C relays.

Pin Descriptions

Input Signal Pins 1 to 6

Pins 1 to 6 are reserved for the input signal conditioner.

See the data sheet for the selected input signal conditioner.

Pins 8 to 15 Relay Output Pins

Pin 8 SP3 NO. Normally Open 5 Amp Form A.

Pin 9 SP1/3 COM. Common for SP1 and SP3.

Pin 10 SP1 NC. Normally Closed 10 Amp Form C.

Pin 11 SP1 NO. Normally Open 10 Amp Form C.

Pin 12 SP4 NO. Normally Open 5 Amp Form A.

Pin 13 SP2/4 COM. Common for SP2 and SP4.

Pin 14 SP2 NC. Normally Closed 10 Amp Form C.

Pin 15 SP2 NO. Normally Open 10 Amp Form C.

Pins 17 to 21 Rear Panel Switches

Pin 18 ANALOG OUTPUT (). mA (0 to 20 mA/4 to 20 mA) or V (0 to 10 V) output is header selectable.

Pin 19 Programming LOCK. By connecting the LOCK pin

to the COMMON pin, the meter's programmed parameters can be viewed but not changed.

Pin 20 COMMON. To activate the LOCK or DIM functions from the rear of the meter, the respective pins have to be connected to the COMMON pin. This pin is connected to the internal power supply ground.

Pin 21 DIM. By connecting the display dim (DIM) pin to the COMMON pin, the display brightness setting is halved.

Pins 23 and 24 AC/DC Power Input

Auto-sensing AC/DC power supply. For voltages between 85-265 V AC / 95-370 V DC (PS1) or 18-48 V AC / 10-72 V DC (PS2).

Pin 17 ANALOG OUTPUT (+). mA (0 to 20 mA/4 to 20 mA) or V (0 to 10 V) output is header selectable.

Pin 23 AC Neutral / DC. Neutral power supply line.

Pin 24 AC line / +DC. Live power supply line.

FL-B101D40PS DS (FL10)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 11

Component Layout

Connectors

WARNING

AC and DC input signals and power supply voltages can be hazardous.

Do Not connect live wires to terminal blocks, and do not insert, remove or handle terminal blocks with live wires connected.

Standard plug-in screw terminal blocks provided by Texmate:

Page 12

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

FL-B101D40PS DS (FL10)

I-Series Input Signal Conditioning Modules

Many additional input modules are available and others are constantly being developed. Check with your local distributor or www.texmate.com for updated information.

Pre-calibrated I-Series input modules, that have span or zero potentiometers, can be interchanged between any I-Series compatible meter, without recalibration, because all of the analog scaling and reference circuitry is self-contained within the module. Where appropriate, all the standard ranges shown are designed to be header selectable by the user, and Texmate's unique SPAN ADJUST Header facilitates scaling to almost any required engineering unit. See Input Module Component Glossary and Calibration on pages 16-17.

Unless otherwise specified Texmate will ship all modules pre-calibrated with factory preselected ranges and/or scalings as shown in BOLD type. Other pre-calibrated standard ranges or custom ranges may be ordered. Factory installed custom scaling and other custom options are also available (see Ordering Information, Special Options on last page).

Symbols Indicate Module Compatibility Within Meter Families

ALL MODELS

SOME MODELS MODEL SPECIFIC

IA01: AC Volts Scaled RMS, 200/600V AC

IA06: AC Volts True RMS, 300/600V AC

IA02: AC Volts Scaled RMS, 200mV/2V/20V AC

IA07: AC Volts True RMS, 200mV/2V/20V AC

IA03: AC Milliamps Scaled RMS, 2/20/200mA AC

IA08: AC Milliamps True RMS, 2/20/200mA AC

IA04: AC Amps Scaled RMS, 1 Amp AC IA05: AC Amps Scaled RMS, 5 Amp AC

IA09: AC Amps True RMS, 1 Amp AC IA11: AC Amps True RMS, 5 Amp AC

Fully User Scalable

FL-B101D40PS DS (FL10)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 13

I-Series Input Signal Conditioning Modules

IA10 AC Millivolts, Scaled RMS, 100mV AC

ID05: DC Volts 2/20/200/Custom V DC with Offset and 24V Exc.

Fully User Scalable

IA12: AC Millivolt RMS Sigma Delta

ID07: DC Milliamps, 2/20/200mA DC with Offset and 24V Exc

ID01: DC Volts, 2/20/200V/Custom w/24V DC Exc

IGYZ: Universal Direct Pressure (Absolute or Differential/Gage)

See below for ordering code options

ID02: DC Millivolts, 20/50/100/200mV DC w/24V DC Exc

Ordering Code Options for Direct Pressure (IGYX, IGYY & IGYZ)

ID03: DC Milliamps, 2/20/200mA DC w/24V DC Exc

IP01: Process Loop, 4-20mA IP02: Process Loop, 4-20mA with 24VDC EXC

Fully User Scalable

IP03: Process Input, 1-5V DC with Offset, 24V Exc

ID04: DC Amps, 5A DC ID09: DC Amps, 1A DC

Fully User Scalable

Fully User Scalable

Page 14

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

FL-B101D40PS DS (FL10)

I-Series Input Signal Conditioning Modules

IP07: Universal Process Input 2V/5V/10V/20V/200V/2mA/20mA/Custom

IS04: Pressure/Load Cell Ext Exc., 20/2mV/V, 4/6wire

IPT1: Prototype Board for Custom Design

IS05: Pressure/Load Cell 20/2mV/V, 5/10V Exc 4-wire

IR02: 3 wire Potentiometer 1K min (0-F.S.)

IS06: Pressure/Load Cell Ext Exc., 20/2mV/V, 4-wire

IS07: Pressure/Load Cell Ext Exc. High Impedance,

20/2mV/V, 4/6wire

IR03: Linear Potentiometer 1K min

IR04: Resistance 2K (Lynx only) IR05: Resistance 2K (Leopard only)

IS01: Strain Gage 5/10VDC Exc., 20/2mV/V, 4/6-wire IS02: Pressure/Load Cell

5/10VDC Exc., 20/2mV/V, 4/6-wire

FL-B101D40PS DS (FL10)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 15

Input Module Component Glossary

Input and Output Pins

On most modules Pin 1 is the Signal High input and Pin 3 is the Signal Low input. Typically Pin 2 is used for Excitation Voltage output.

INPUT RANGE Header

Range values are marked on the PCB.Typically two to four positions are provided, which are selected with either a single or multiple jumper clip. When provided, a custom range position is only functional when the option has been factory installed.

SPAN Potentiometer (Pot)

If provided, the 15 turn SPAN pot is always on the right side (as viewed from the rear of the meter).

Typical adjustment is 20% of the input signal range.

SPAN ADJUST Header

This unique five-position header expands the adjustment range of the SPAN pot into five equal 20% steps, across 100% of the input Signal Span.

Any input Signal Span can then be precisely scaled down to provide any required Digital Display span from 1999 counts to 001 (one count).

24V DC Output Header

On some modules this header enables a 24V DC 25mA (max) Excitation/Auxiliary output to be connected to Pin 2.

ZERO Potentiometer (Pot)

If provided, the ZERO pot is always to the left of the SPAN pot (as viewed from the rear of the meter). Typically it enables the input signal to be offset 5% of full scale (-100 to +100 counts).

ZERO OFFSET RANGE Header

When provided, this three position header increases the ZERO pots capability to offset the input signal, to 25% of the digital display span. For example a Negative offset enables a 1 to 5V input to display 0 to full scale. The user can select negative offset, positive offset, or no offset (ZERO pot disabled for two step non-interactive span and offset calibration).

SPAN RANGE Header

When this header is provided it works in conjunction with the SPAN ADJUST Header by splitting its adjustment range into a Hi and a Lo range. This has the effect of dividing the adjustment range of the SPAN pot into ten equal 10% steps across 100% of the input Signal Span.

Page 16

ZERO ADJUST Header

When this header is provided, it works in conjunction with the ZERO OFFSET RANGE Header, and expands the ZERO pots offset capability into five equal negative steps or five equal positive steps.

This enables virtually any degree of input signal offset required to display any desired engineering unit of measure.

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

FL-B101D40PS DS (FL10)

Input Module Calibration Procedures

In addition to the analog calibration capabilities that enable many modules to be interchanged between different meters without loss of accuracy the Leopard Family of meters have enhanced Digital Calibration functions.

Large offset scaling and calibration of process signal inputs with modules that utilize ZERO ADJUST Headers and or ZERO OFFSET RANGE Headers.

Basic standard range calibration of direct reading modules that utilize either Auto Zero or a ZERO pot, an INPUT RANGE Header and or a SPAN pot.

1 If the module has an INPUT RANGE Header, reposition the

jumper clip to select the desired input signal range.

2. Apply a zero input or short the input pins. The display will auto zero, or if the module has a ZERO pot, it should be adjusted until the display reads zero.

3 Apply a known input signal that is at least 20% of the full scale input range and adjust the SPAN pot until the display reads the exact input value. For negative inputs, Leopard Family Meters will display negative overrange at 50% of full scale range.

4 Decimal Points.The selection or positioning of decimal points has

no effect on the calibration of the modules

Wide range scaling, in engineering units not requiring offsets, with modules that utilize auto-zero or a ZERO pot, a SPAN RANGE Header and or a SPAN ADJUST Header.

Texmates unique SPAN ADJUST and SPAN RANGE Headers provide the circuit equivalent of an ultra-precision one megohm 75 or

150 turn potentiometer that can infinitely scale down any Input Signal SPAN to provide any full scale Digital Display Span from

1999 (counts) to 001 (one count).

If the module has an INPUT RANGE Header, and the required full scale Digital Display Span (counts) is to be larger than the directly measured value of the input Signal Span, then the next lower range on the INPUT RANGE Header should be selected. The resulting over range Signal Span is then scaled down, by selecting the position of the SPAN RANGE Header and or the SPAN ADJUST Header, which will reduce the input Signal Span to a percentage, that the required Digital Display Span can be reached by calibration with the SPAN pot.

Example A: 0 to 10 V to read 0 to 1800 gallons.

Signal Span = 10V, Digital Display Span = 1800 counts

1 Select the 2 V INPUT RANGE Header position. This will provide a digital display of 1800 counts with an input of only 1.8 V which is (1.810)=18% of the examples 10 V Signal Span.

2 To scale down the Signal Span to 18% select the 20% Signal Span position on the SPAN ADJUST Header (position 1) or if the module has a SPAN RANGE Header, select (LO Range) and 20% Signal Span position on the SPAN ADJUST Header (position 2).

3 Apply a zero input or short the input pins. The display will auto zero, or if the module has a ZERO pot, it should be adjusted until the display reads zero.

4 Apply 10 V and adjust the SPAN pot until the display reads 1800.

Texmates unique ZERO OFFSET RANGE Header enables the use of a simple two step scaling and calibration procedure for those process signals that require large offsets. This eliminates the back and forth interaction, between zero and span settings, that is often required to calibrate less finely engineered products.

The first step is to set the ZERO OFFSET RANGE Header to the center position (No Offset) and scale down the Input Signal Span to a percentage that will enable calibration with the SPAN pot to reach the required Digital Display Span.

The second step is to set the ZERO ADJUST and or ZERO OFFSET RANGE Header to provide a positive or negative offset of sufficient counts that calibration with the ZERO pot will offset the Digital Display Span to produce the required digital reading.

Example B: 1 to 5 V to read 100 to 1500 C.

Signal Span = 4V, Digital Display Span = 1600 counts

1 If the module has an INPUT RANGE Header the 2 V position should be selected. This will provide a digital display of 1600 counts for an input of 1.6 V which is (1.6 4) = 40% of the examples 4 V signal span. To scale down the Signal Span to 40% select the 40% Signal Span position on the SPAN ADJUST Header (position 2).

2 If the module is a Process Input 1-5 V DC type, select the (Hi Range) position on the SPAN RANGE Header and the 100% Signal Span position on the SPAN ADJUST Header (position 5, max increase).

This will provide a digital display of 1600 counts for an input of 4V which is 100% of the examples 4V Signal Span.

3 Set the ZERO OFFSET RANGE Header to the center position (no offset). Apply 1 V and adjust the SPAN pot until the display reads 400. A 4V input would then read 1600 counts.

4 Set the ZERO OFFSET RANGE Header to the negative offset position. If the module has a ZERO ADJUST Header select the position that will provide a negative offset of 500 counts.

Apply 1 V and adjust the ZERO pot until the display reads 100. Apply 5 V and check that the display reads 1500.

Example C: 4 to 20 mA to read 00.0 to +100.0% Signal Span = 16 mA, Digital Display Span = 1000 counts.

1 The full scale Signal Span of the Process Input 4-20 mA modules is 0 to 20 mA for a full scale Digital Display Span of 0 to 2000 counts. This will provide a digital display of 1000 counts with an input of only 10 mA which is (1016)=62.5% of the examples 16 mA signal span.

2 To scale down the Signal Span to 62.5% select the (Hi Range) Position on the Span Range Header and the 70% Signal Span position on the SPAN ADJUST Header (position 2).

3 Set the ZERO OFFSET RANGE Header to the center position (no offset). Apply 4 mA and adjust the SPAN pot until the display reads 250. A 16 mA input would then read 1000 counts.

4 Set the ZERO OFFSET RANGE Header to the positive offset position. If the module has a ZERO ADJUST Header select the position that will provide a negative offset of 250 counts. Apply

4 mA and adjust the ZERO pot until the display reads 000. Apply

20 mA and check that the display reads 1000.

FL-B101D40PS DS (FL10)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 17

Ordering Information

BASIC MODEL #

DISPLAY

POWER SUPPLY

INPUT MODULES

ANALOG OUTPUT

RELAY OUTPUT

OPTIONS / ACCESSORIES

FL-B101D40PS

OA____

Add to the basic model number the order code suffix for each standard option required. The last suffix is to indicate how many different special options and or accessories that you may require to be included with this product.

Ordering Example: FL-B101D40PS-VRR-PS1-IA01-OIC-R11-OA2 plus CR-CHANGE and an OP-N4/144X36

Tel: 1-760-598-9899 USA 1-800-839-6283 Thats 1-800-TEXMATE Fax: 1-760-598-9828 Email: [email protected] Web: www.texmate.com

For Custom Face Plates and Scales see page 19.

For product details visit www.texmate.com

Local Distributor Address

Page 20

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

FL-B101D40PS DS (FL10)

About TexMate

Texmate is an American manufacturer of high durability industrial grade panel meters, bar graphs, and transducers. Texmate's meters are frequently equipped with relays and various signal outputs for industrial automation applications and are known for their extremely long service life.