FI-B101D50E & FI-B101D50T

Programmable Meter Controllers

Tiger 320 Series PMCs

101 Segment Bargraph, 5 Digit 0.31 LEDs

in a 9/64 DIN Case

TIGER FAMILY

A powerful, intelligent, 5-digit, 101-segment Programmable

Meter Controller (PMC) with modular outputs, input signal

conditioning and advanced software features for monitoring, mea-

surement, control and communication applications.

General Features

The Tiger 320 Operating System supports an easy to use PC based Configuration Utility Program (which can be downloaded FREE from the Texmate website) and programming from front panel buttons.

The T Version supports custom macro programs that can be easily produced with the Tiger 320 Macro Development System (available FREE on the Texmate website). The Development System enables programs to be written in BASIC, which can utilize any combination of the hundreds of functions and thousands of registers embedded in the Tiger 320 Operating System.

Red 7-segment, 0.31 high LEDs with full support for seven

segment alphanumeric text.

Brightness control of LED display from front panel buttons.

101 segment red, green or tricolor bargraph that can display the signal from any of four channels or the result of a processed input signal.

Modular construction with more than 120 interchangeable

input signal conditioners.

Up to 4 input channels with cross channel math for multi-

channel processing.

For applications where sensor excitation is required, modules

are provided with 5V, 10V or 24 V DC voltage outputs.

Auto-sensing high voltage or optional low voltage AC / DC

power supply.

Serial output options include RS-232, RS-485, ModBus or

direct meter-to-meter communications.

Single or dual 16-bit Isolated Analog Outputs. Programmable 0~4 to 20mA or 0 to 10V for retransmission, 4-20mA loops to drive valve actuators, remote controllers & displays, multi-loop feedback and PID output. Scalable from 1 count to full scale.

Dual independent totalizers to integrate input signals.

6 super smart, independently programmable setpoints with 8 selectable functions, including latching, deviation, hysteresis, register resetting, tracking and dual PID. Plus 7 programmable timer modes on all 6 setpoints.

Setpoint tracking, setpoint latching and manual relay reset.

Setpoints activated from any input, any register in the meter or

from any digital input.

Up to 4 independent programmable electromechanical and

solid state relays.

Internal program safety lockout switch to prevent tampering.

Peak & valley (max & min) with front panel recall and reset.

Real time clock with 15 year Lithium battery backup.

Data logging within the meter (up to 4000 samples with date/

On demand tare, calibration and compensation can be initiated

time stamp).

by the front panel program button.

Autozero maintenance for super stable zero reading is provid-

ed for use in weighing applications.

Programmable input averaging and smart digital filtering for

quick response to input signal changes.

Display

text

editing. Customize

display

text

for

OEM applications.

Scrolling display text messaging on T meters with macros.

Optional NEMA-4 front cover.

UL Listed

Input Module Compatibility

TIGER FAMILY: More than 120 different Plug-in I-Series Input Signal Conditioners are approved for the Tiger Family of meters.

See I-Series Input Signal Conditioning Modules Guide (Z87) for an up-to-date list.

General Features................... 1 Specifications..................... 2-3 Block Diagram of Tiger 320 Structure... 4 Controls & Indicators............... 5-6 Front Panel Configuration & Setup...... 7 Front Panel Programming Codes..... 8-9 Initial Setup Procedures.......... 10-11 Display Brightness.................. 11 Calibration Modes............... 12-15

Table of Contents

Programming Procedures......... 16-34 Setpoint Programming Mode...... 35-41 Registers......................... 42 Functional Diagram................. 43 Connector Pinouts.................. 43 Carrier Board Output Pins........... 44 Relay Options..................... 44 Component Layout & Ext. Devices... 45-46 Installation Guidelines............... 47

Index......................... 48-49 Case Dimensions.................. 50

Page 1

Specifications

Display

Digital Display: 7-segment, 0.31 (8 mm) LEDs.

Display Color: Red

Digital Display Range: -19999 to 99999

Update Rate: 3 to 10 times per second

Bargraph Display: 101-segment bargraph.

Bargraph Color: Red (std). Green or Tricolor (optional).

Display Dimming: 8 brightness levels. Front Panel selectable

Scrolling Display Text Messaging: Full alphanumeric, 7-segment text characters supported on T Version with macros.

Polarity: Assumed positive. Displays - negative

Decimal Point: Front panel, user selectable to five positions.

Overrange Indication:

Underrange Indication:

Front Panel Controls: PROGRAM, UP and DOWN.

Operating System (Tiger 320)

Processor: 32 bit with floating point maths (18.4 MHz).

Flash Memory: 64k, 4k for use by custom macros.

RAM: 1.25k and FeRAM 4k.

EEPROM: E Version 4k standard, T Version 32k standard. Memory upgrades available to 32k for LIN Tables and 1MB for Data Logging and custom macros.

Registers: 6144 registers comprised of 8, 16 or 32 bit signed, unsigned or floating point registers, implemented in a combination of RAM, FeRAM, Flash and EEPROM.

Internal communication BUS: 32 bit I2C BUS

Development System for Custom

Macros

The Tiger 320 Macro Development System, which may be downloaded free from our website, can be used to create powerful macro software that allows Tiger 320 T Versions to be easily customized to suit any proprietary OEM application.

Installed Application Software

Includes

Counter Functions: Two built-in counters. UP counters, DOWN counters, UP/DOWN counters and high speed quadrature counters.

Data Logging: Logging with a date/time stamp, initiated at timed intervals, by activation of a setpoint, or manually. Data stored in internal 1MB EEPROM or in a removable 4 to 128M Flash Card Memory Module.

Endless loop recording is supported.

Input Compensation: Provides compensation to the primary input channel (CH1) via channels 2, 3 or 4.

Linearization: 4 selectable 32 point or one 125 point flexible linearization tables are provided.

Logic I/O: 28 Macro programmable I/O ports supported.

Manual Loader: Front panel adjustable, 4 to 20mA or

0 to 10V isolated analog output.

Math Functions: Cross channel math functions to calculate the sum, difference, ratio or the product of two inputs.

On Demand Functions: Tare, compensation and calibration.

Peak and Valley: The meter can retain peak and valley (min/max) information and recall this on the front panel.

Remote Setpoint Input: Remote setpoint input via channel 2.

Serial Output Protocols: Selectable communication modes include ASCII, Modbus (RTU), Master Mode (for meter to meter communication) and an Epson compatible printer driver.

Setpoint Functions: Six super smart setpoints with fully configurable hysteresis, on and off delays, one shot, pulse and repeat timers, latching, dual PID, setpoint tracking, resetting of registers, initiating of logging and printing.

Signal Conditioning Functions: Averaging, smart filter, rounding, square root,auto zero maintenance.

Timer: Timer functions supported in either time-up, time-down, or real-time clock modes.

Totalizer: Two totalizers for running total and batch totals of a process signal that can be accumulated over time.

Time

(option): Real

Year:Month:Date:Hour:Minute:Second with 15 yr Lithium battery backup.

Clock

Configuration: Supports Front Panel Programming Codes and a PC-based Configuration Utility Program, which may be downloaded free from our website. T Version also supports custom macros.

Page 2

Specifications continued

Inputs

Inputs Available: More than 120 single, dual, triple and quad input signal conditioners available covering all types of analog, digital and mixed input signals.

Accuracy: Tiger 320 PMCs enable the user to establish any degree of system accuracy required. Built-in compensation and linearization functions enable system accuracies of the order of 0.0001% of reading for analog inputs. Stop -Start time resolution from 1sec to 0.7nsec. Digital input and pulse counts 1 count.

A/D Convertors: A Dual Slope, bipolar 17 bit A/D is provided as standard on the main board. SMART modules can have 24 bit or 16 bit Delta-Sigma A/D convertors that utilize the internal I2C BUS.

Temperature Coefficient: Typically 30ppm/ C.

Compensation can be utilized to achieve system temperature coefficients of 1ppm.

Warm Up Time: Up to 10 minutes, depending on input module.

Conversion Rate: Typically 10 samples per second.

However, SMART input modules are available that can convert at 60, 240, 480 or 960 samples per second.

Control Output Rate: Can be selected for 100msec or 10msec. Some SMART modules have SSR outputs that react within 1.2msec.

Excitation Voltage: Depends on input module selected. Typically, 5V, 10V or 24VDC is provided.

Outputs

(See pages 44-46 for pinouts and details of modular construction)

Carrier Board: Provides three different serial outputs or no serial output and supports single or dual analog outputs.

Standard Carrier Board: Is available without a serial output, or with either an isolated RS-232 or an isolated RS-485 (RJ-6 socket).

Two Isolated Analog Output Options: Mounted on any

carrier board.

1. Single Analog Output: Fully scalable from 4 to 20mA or 0 to 20mA (or reverse) and selectable for 0 to 10VDC (or reverse).

2. Dual Analog Output: Fully scalable from 0 to 10VDC (or reverse).

Outputs continued

Analog Output Specifications: Accuracy: 0.02% FS. Resolution: 16-bit Delta-Sigma D/A provides 0.4A on current scaling, 250V on voltage scaling.

Compliance: 500 maximum for current output.

500 minimum for voltage output. Update Rate:

Typical 7 per second. Step Response: Typical 6msec to a display change. Scalable: From 1 count to full scale.

Power Supplies

Auto sensing AC/DC (DC to 400Hz) hi volts std, low volts optional.

PS1 (standard): 95-300VDC / 85-265VAC, 50-400Hz, 3.5W nominal.

PS2 (optional): 10-72VDC / 14-48VAC, 50-400Hz, 3.5W nominal.

Environmental (See Rear page for IP-65 & NEMA-4 options)

Operating Temperature: 0 to 50 C (32 F to 122 F).

Storage Temperature: -20 C to 70 C (-4 F to 158 F).

Relative Humidity: 95% (non-condensing) at 40 C (104 F).

Mechanical (See Rear page for more details)

Case Dimensions: 9/64 DIN, 144x36mm (5.69 x 1.42)

Case Material: 94V-0 UL rated self-extinguishing polycarbonate.

Weight: 11.5 oz (0.79 lbs), 14 oz (0.96 lbs) when packed.

Certifications and Listings

CE: As per EN-61000-3/4/6 and EN-61010-1.

UL: E469078

Page 3

Block Diagram of the Tiger 320 Series Software and Hardware Structure

Page 4

Controls and Indicators Controls and Indicators 2

Front Panel Controls and Indicators

Program Button

While programming, pressing

the P button saves the current programming settings

and moves to the next programming step.

You can move through the programming codes using the program button. The codes you pass are not affected, unless you stop and make changes using the

buttons.

Pressing the P and button at the same time initiates the main programming mode.

To save a new configuration setting and return to the operational display, press

the P button

button at the same time.

once and then press the P and Pressing the P and button at the same time initiates the setpoint programming mode. To save a new configuration setting and return to the operational display, press the P button once and then press the P and button at the same time.

See Display with Faceplate and Bezel diagram.

Up Button

When setting a displayed parameter during programming, press the

button to increase the value of the displayed parameter.

When in the operational display, pressing the button initiates a viewing mode that allows you to view the readings on channels 1 and 3, setpoints 1, 3, and 5, peak, and total 1. Once into the viewing routine, pressing the button moves through each displayed parameter.

See Display with Faceplate and Bezel diagram.

button to decrease the value of the displayed parameter.

Down Button

When setting a displayed parameter during programming, press the

When in the operational display, pressing the button initiates a viewing mode that allows you to view the readings on channels 2 and 4, setpoints 2, 4, and 6, valley, and total 2. Once into the viewing routine, pressing the button moves through each displayed parameter.

See Display with Faceplate and Bezel diagram.

Annunciator LEDs

The annunciator LEDs can be programmed to indicate the alarm status.

Setpoint 1 can be configured to indicate the rising signal trend.

Setpoint 2 can be configured to indicate the falling signal trend.

They are labeled from left to right: SP1, SP2, SP3, SP4, SP5, SP6.

See Display with Faceplate and Bezel diagram.

LED Display

The five, seven segment digital display LEDs are used to display the meter input signal readings and programming codes and settings during programming. The digital display is known as the primary display during programming. The display is available in red LEDs.

Bargraph Display

The bargraph display is a 101 segment red, green, or tri-color bargraph that can display the signal from any of four channels or the result of a processed input signal. The bargraph display is known as the secondary display during programming.

When the PROGRAM LOCKOUT switch is set to position 2, all programmable meter functions can be changed.

Program Lockout Switch

When set to the ON position, the PROGRAM LOCKOUT switch 2 prevents any programming changes being made to the meter. If programming is attempted, the meter displays [LOC]. The ON position allows programming parameters to be viewed but not changed.

See Display without Faceplate and Bezel diagram.

Display Text Editing with 7 Segment Alphanumeric Display Characters

Display text, such as setpoints, can be easily edited to suit your application, by connecting the meter to a PC running the free downloadable Configuration Utility program.

For Example:

Instead of [SP_1]

Instead of [SP_2]

could be used for TANK LOW

could be used for BRAKE OFF

Scrolling Display Text Messaging Scrolling display text messaging can be configured to run but requires a simple compiler generated macro.

Display Text Characters

The following text characters are used with the 7-segment display.

7-SEGMENT DISPLAY CHARACTERS

Page 5

Controls and Indicators continued Controls and Indicators

Setpoint Lockout Switch

When the SETPOINT LOCKOUT switch 1 is set to the ON position, the setpoints can be programmed. Once the setpoint values have been entered and the SETPOINT LOCKOUT switch set to the ON position, the setpoints can be viewed but not changed.

See Display without Faceplate and Bezel diagram.

Error Message [Err]

Error messages usually occur during calibration procedures.

The three most likely causes of an error message are:

1) The full scale and zero signals were too similar.

Note, the high input (full scale) signal must be at least 1000 counts greater than the low input

(zero) signal (positive and negative values are allowed).

2) The scaling requirement exceeded the capability of the meter (19999 to +99999).

3) No input signal present, or incor-

rect connections.

The main programming mode can be entered, but only the brightness setting adjusted. After adjusting the brightness setting, pressing the P button displays [LoCK].

The LOCK pin can also be configured in Code 9 to carry out the following functions (see Meter Programming Codes on Page 9):

Reset channel 1 [XX1].

Reset channel 2 [XX2].

Reset channel 3 [XX3].

Reset channel 4 [XX4].

Reset tare [XX5].

Reset total 1 [XX6].

Unlatch (de-energize) all setpoints [XX7].

Hold Pin

Configure Code 9 to [X0X]. When the HOLD pin (pin 9) is connected to the COMMON pin (11) the displayed reading is frozen.

However, A/D conversions and all control functions continue and as soon as pin 9 is disconnected from pin 11 by the switch, the updated reading is instantly displayed.

The HOLD pin can also be configured in Code 9 to carry out the following functions (see Meter Programming Codes on Page 9):

Reset channel 1 [X1X].

Reset total 1 and total 2 [X2X].

Rear Panel External Switched Inputs

Lock Pin

By configuring Code 9 to [XX0], connecting the LOCK pin (pin 8 on the main PCB) to the COMMON pin (pin 11 on the main PCB), locks out the main and setpoint programming modes. All meter programming codes and setpoints can be viewed but not changed.

Reset total 2 [X3X].

Reset peak and valley [X4X].

Reset tare [X5X].

Set tare [X6X].

Unlatch (de-energize) all setpoints [X7X].

Test Pin

Configure Code 9 to [0XX]. When the TEST pin (pin 10) is connected briefly to the COMMON pin (pin 11) all segments of the display and setpoint annunciators light up. Six eights and six decimal points (8.8.8.8.8.8.) are displayed for a short period. The microprocessor is also reset during this time, losing all RAM settings such as peak and valley, and any digital input pin settings set up in Code 9.

The TEST pin can also be configured in Code 9 to carry out the following (see Meter Programming Codes on Page 9):

Reset counter channel 1 and total 2 at power-up [1XX].

Reset counters, CH1, CH2, CH3, CH4,- total 1, and total 2 at

power-up [2XX].

Reset total 1 and total 2 at power-up [3XX].

Capture Pin

When the CAPTURE pin (pin 12) is connected to the COMMON pin (pin 11), the CAPTURE pin can be programmed for setpoint/ relay activation or macro control applications in the setpoint control settings mode of the setpoint programming mode [SPCX] [X2X].

Common Pin

To activate the LOCK, HOLD, TEST and CAPTURE pins from the rear of the meter, the respective pins have to be connected to the COMMON pin (pin 11).

Page 6

Front Panel Push Button Configuration and Setup for Programming Conventions

Third

Digit

First

Digit

Second

Digit

The meter uses a set of intuitive software codes to allow maximum user flexibility while maintaining an easy programming process.

To configure the meters programming codes, the meter uses the three right-hand side display digits. These are known as the 1st, 2nd, and 3rd digits and can be seen in the diagram opposite. To explain software programming procedures, diagrams are used to visually describe the programming steps.

The following conventions are used throughout the range of Tiger 320 Series document diagrams to represent the buttons and indicators on the meter, and the actions involved in programming the meter:

Operational Display

Symbol

Explanation

The digital display showing 99999 represents the OPERATIONAL DISPLAY.

After the meter has been powered up, the display settles and indicates the calibrated input signal. This is known as the operational mode and is generally referred to as the operational display throughout the documentation.

All programming modes are entered from this level.

This symbol represents the PROGRAM button. In a procedure, pressing the program button is always indicated by a left hand. A number indicates how many times it must be pressed and released, or for how long it must be pressed before releasing.

Programming procedures are graphic based with little descriptive text.

Each procedure shows a number of meter panel displays running in procedural steps from the top to the bottom of the page.

If need be, the procedure may run into two columns with the left column running down the page and continuing at the top of the right-hand column. Each action performed by the user is shown as a numbered step.

Each procedural step shows the meter display as it looks before an action is performed. The hand or hands in the procedural step indicate the action to be performed and also how many times, or for how long, the button is to be pressed.

For example, the diagram to the right shows the meter in the operational display.

With a left hand pressing the P button and a right hand pressing the button, the user is entering the main programming mode. This is indicated by the next diagram displaying [bri] and [5].

This is the display brightness mode and is the first submenu of the main programming mode.

Step 1

Step 2

Where a left and right hand are shown on separate buttons on the same diagram, this indicates that the buttons must be pressed at the same time.

The only exception to this rule is when carrying out the Model and Software Code Version Check.

When two displays are shown together as black on grey, this indicates that the display is toggling (flashing) between the name of the function and the value or configuration setting.

Where a number is not definable, the default setting [000] is shown.

This symbol represents the UP button.

Shown in a diagram, pressing the UP button is always indicated by a right hand.

This symbol represents the DOWN button.

Shown in a diagram, pressing the DOWN button is always indicated by a right hand.

Where two right hands are shown on the same diagram with the word OR between them, this indicates that both the buttons can be used to adjust the display: UP for increase, DOWN for decrease.

and

[Span]

[10000]

Text or numbers shown between square brackets in a description or procedure indicate the programming code name of the function or the value displayed on the meter display.

If an X appears in the description of a 3-digit programming code or in a configuration procedure, this means that any number displayed in that digit is not relevant to the function being explained, or more than one choice can be made.

Page 7

Front Panel Programming Codes

The meters programming codes are divided into two modes: the main programming mode, and the setpoint programming mode (See Diagram below). Each mode is accessible from the operational display.

Main Programming Mode

The main programming mode provides access to program all meter functions, except setpoints.

To enter or exit the Main Programming Mode, press

at the same time P and

Main Programming Mode

Display Brightness

[bri]

[CAL]

Calibration Modes for Input and Output

[Cod_1]

Code 1 Display Configuration

[Cod_2]

Code 2 CH1 Measurement Task & Sampling Rate

[Cod_3]

Code 3 CH1 Post Processing & Serial Mode Functions

[Cod_4]

Code 4 CH2 Measurement Task & Sampling Rate

[Cod_5]

Code 5 CH3 Functions

[Cod_6]

Code 6 CH4 Functions

[Cod_7]

Code 7 Result Processing

Programming Tip

Save Code Settings & Exit

[Cod_8]

Code 8 Data Logging & Print Mode

[Cod_9]

Code 9 Functions for Digital Input Pins

[Cod10]

Code 10 Bargraph Setup

Page 8

Programming Tip

The easiest and fastest way to configure the Tiger 320 is to use a PC with the free downloadable configuration utility program.

Setpoint Programming Mode

The setpoint programming mode provides access to program all setpoint and relay functions.

To enter or exit Programming Mode, press P and at the same time

the Setpoint

Setpoint Programming Mode

Setpoint Activation Values Mode

Programming Tip

[SP_1]

Setpoint 1

[SP_2]

Setpoint 2

[SP_3]

Setpoint 3

[SP_4]

Setpoint 4

time to exit.

[SP_5]

Setpoint 5

[SP_6]

Setpoint 6

Setpoint & Relay Control Settings Mode

[SPC_1]

Setpoint 1

[SPC_2]

Setpoint 2

[SPC_3]

Setpoint 3

[SPC_4]

Setpoint 4

[SPC_5]

Setpoint 5

[SPC_6]

Setpoint 6

Front Panel Programming Codes continued

the operation-

View Modes

While

al display, pressing the button allows you to view but not change the following parameters:

Channel 1.

Channel 3.

Setpoint 1.

Setpoint 3.

Setpoint 5.

Peak (of CH1).

Total 1 (total of CH1).

the operation-

While

al display, pressing the button allows you to view but not change the following parameters:

Channel 2.

Channel 4.

Setpoint 2.

Setpoint 4.

Setpoint 6.

Valley (of CH1).

Total 2 (total of CH2).

On Demand Modes

The meter can be programmed to activate the following functions on demand by pressing the P button for 4 seconds:

Tare.

Single-point calibration.

Two-point calibration.

Primary input compensation.

Manual loader (manual offset).

Print.

The on demand function is selected in the calibration mode.

Pressing both the buttons at the same time while in either the peak, valley, total 1, or total 2 view modes resets the setting to the current displayed signal.

and

Operational Display

Operational Display

Operational Display

Press

Press

To view, press

button: the

View Mode

To view, press

button: the

View Mode

Ch1

Ch3

SP_1

SP_3

SP_5

PEAK

tot_1

Ch2

Ch4

SP_2

SP_4

SP_6

VALEY

tot_2

After configuring an on demand the function

Calibration On Demand

Mode, press the P button for

4 seconds to activate one of the following selected on demand modes.

On Demand Modes

Tare

Single-point calibration

Two-point calibration

Primary input compensation

Manual loader (manual offset)

Print

For a full breakdown of all programming codes, see the Tiger 320 Series Programming Code Sheet (NZ101).

Page 9

Initial Setup Procedures Initial Setup Procedures

Before configuring the meter, carry out the following meter configuration checks:

Model and software code version check.

Code blanking and macro check.

After powering-up the meter, check the model and software code version number and note this in your user manual.

Model and Software Code Version Check The meter model and software code version number can be checked at any time while in the operational display using the following procedure.

START HERE

MODEL &

SOFTWARE CODE

VERSION CHECK

Example

Programming Tip

The Model and Software Code Version checking procedure can be performed at any time without interfering with other configuration settings.

Page 10

Code Blanking and Macro Check

320 Series meters have the ability to hide (blank out) all or some programming codes, making them tamper-proof. This can only be done using the Meter Configuration program.

With code blanking turned ON, all main and setpoint codes that have been blanked out during factory programming are hidden, preventing them from being reprogrammed. Any codes that have not been blanked out are still visible and can be reprogrammed.

Turning code blanking OFF means all meter programming codes are visible when you enter the programming modes and can be reprogrammed.

A macro is a set of commands that run automatically when the meter is powered up. We have a growing library of macros to suit a wide range of standard customer applications.

Macros can be installed in the meter at the factory during initial programming or by the customer at some later date. Macros are written and compiled using the BASIC Compiler program, and loaded into the meter using either the BASIC Compiler program or the Meter Configuration program.

Turning the macro OFF means that the meter will not perform the automatic commands pre-programmed to run with the macro.

Unless requested to blank out all or some programming codes and/or run a macro, we will program the meter in the code blanking OFF and macro OFF (default) setting.

To turn the code blanking and macro settings from ON to OFF:

START HERE

CODE BLANKING

& MACRO CHECK

PROCEDURE

Initial Setup Procedures continued Initial Setup Procedures CODE BLANKING & MACRO CHECK PROCEDURE 1

[bri] - Display Brightness Initial Setup Procedures

Programming Tip

Code Blanking and Macro ON/OFF settings revert to the meters original configuration settings when the meter is powered off and on.

Display Configuration

Once you have read the user manual and related supplements, and installed and powered-up the meter, configure the display

to suit its designated application.

Display Brightness Mode

The display brightness mode is accessed when entering the main programming mode. It allows you to adjust the brightness of the display LEDs and setpoint annunciators without interfering with other configuration settings. It is always available, even with the PROGRAM LOCK switch set to ON, or the external LOCK pin connected to the COMMON pin, locking out the programming modes.

The display brightness can be set between 0 and 3, with 0 being dull and 3 being bright. The default setting is 2.

CONFIGURING THE DISPLAY BRIGHTNESS PROCEDURE

Example Procedure:

Configure the display brightness setting to 3 (bright).

START HERE

DISPLAY

BRIGHTNESS

MODE

Step 1

Enter

Brightness Mode

Step 2

Step 3

Example

Programming Tip

The Display Brightness setting procedure can be performed at any time without interfering with other configuration settings by entering the main programming mode.

Operational Display

Page 11

[CAL] - Calibration Modes for Input and Output

The Tiger 320 Series meter has an extremely powerful set of input and output calibration modes. See diagram below.

ON DEMAND Functions

In this mode the meter can be programmed to activate one of the following on demand functions by pressing the P button while in the operational display:

On Demand TARE.

On Demand Single-point Calibration (requires single input source).

On Demand Two-point Calibration (requires dual input source).

On Demand Primary Input Compensation Mode.

On Demand Manual Loader Mode.

Page 12

Calibration Modes

The following calibration modes are available:

Manual Calibration (requires NO input source).

Two-point Calibration (requires dual input source).

This is the calibration mode generally used to calibrate the meter for most applications. An example procedure has been included.

Calibrate Thermocouple (requires K type thermocouple

input source).

Calibrate RTD (requires RTD 385 input source).

Calibrate Smart Input Module (not available on all input

modules).

Calibrate Analog Output (requires multimeter connected to pins

16 and 17).

[CAL] - Calibration Modes for Input and Output continued [CAL] - Calibration Modes for Input and Output continued Related Calibration Functions

The following functions are also configured in the calibration mode. See Advanced Calibration and On Demand Mode Supplement (NZ203) for further calibration details.

Serial Communications Properties

Selecting [CAL][20X] enters the Serial Communications Properties Mode.

This mode allows you to configure the serial communications output module baud rate, parity, time delay, and address settings.

See the calibration modes diagram on Page 13 showing a breakdown of 1st, 2nd, and 3rd digits.

Also see the Serial Communications Module Supplement

(NZ202) for further details on the serial communications module.

Set Auto Zero Maintenance Selecting [CAL][21X] enters the Set Auto Zero Maintenance Mode.

This mode allows you to configure auto zero maintenance settings for weighing applications applied to the channel selected in the 3rd digit.

See the calibration modes diagram on Page 13 showing a breakdown of 1st, 2nd, and 3rd digits.

Set Averaging Samples & Averaging Window Selecting [CAL][22X] enters the Set Averaging Samples and Averaging Windows Mode.

This mode allows you to configure the number of input signal samples to average over, and the size of the averaging window in display counts applied to the channel selected in the 3rd digit.

Selecting [CAL][22X] enters the Set Averaging Samples and Averaging Windows Mode. When in this mode, the [AV_S] menu allows you to select the number of input signal samples to average over. After setting the number of samples, moving to the [AV_W] menu allows you to configure the size of the averaging window in displayed counts.

The meter averages the input samples over the selected number of input samples (selected in the [AV_S] menu). This carries on in a continual process provided the input signal stays within the averaging window (set in the [AV_W] menu). If the sample moves out of the averaging window, the meter responds quickly to the change by displaying the non-averaged signal value.

When the signal stabilizes, a new averaging window is established and averaging resumes.

You can program the number of samples you want to average the input signal over from 1 to 255 samples. The averaging window can be set to between 1 and 65535 counts.

See the calibration modes diagram on Page 13 showing a breakdown of 1st, 2nd, and 3rd digits.

See Input Signal Sampling Showing Averaging Window diagram opposite.

Example Procedure

The example procedure on Page 16 shows how to configure channel 1 (CH1) with an averaging sample rate of 10 counts and an averaging window of 1000 counts.

Totalizer Settings

Selecting [CAL][23X] enters the Totalizer Settings Mode.

This mode allows you to configure the settings for the totalizer selected in the 3rd digit. An input value of 10000 counts is applied to a selectable time period to produce the required total value.

The cutoff is a programmable limit below which the input is not totalized.

See the calibration modes diagram on Page 13 showing a breakdown of 1st, 2nd, and 3rd digits.

Also see the Totalizing and Batching Supplement (NZ208) for further details on K factor and totalizer cutoff parameters.

Setup 32-point Linearization Tables Selecting [CAL][24X] enters the Setup 32-point Linearization Tables Mode.

This mode allows you to set up the linearization table or tables using the manual or auto setup modes. The table or tables can then be selected to linearize the signals on channels 1 to 4.

See Linearization Table Notes on Page 34 for a description of memory related issues with linearization.

See the calibration modes diagram on Page 13 showing a breakdown of 1st, 2nd, and 3rd digits.

Also see the Linearizing Supplement (NZ207) for further details on linearization table setup and use.

Scale Analog Output

Selecting [CAL][25X] enters the Scale Analog Output Mode.

This mode allows you to calibrate and scale the analog output signal. Before calibrating the analog output in the calibration mode, the data source for the analog output must be configured in Code 1.

See the calibration modes diagram on Page 13 showing a breakdown of 1st, 2nd, and 3rd digits.

Also see the Analog Output Module Supplement (NZ200) for further details on the analog output module.

Also see Configure Data Source Procedure on Page 22 for an example of setting the analog output data source.

Calibration Mode Procedures Supplement The Advanced Calibration and On Demand Mode Procedures Supplement (NZ203) describes in detail all Tiger 320 Series meter related calibration procedures configured in the calibration mode.

Page 13

[CAL] - Calibration Modes for Input and Output continued [CAL] - Calibration Modes for Input and Output continued

Two-point Calibration

Two-point calibration is the most commonly used method of calibrating Tiger 320 Series meters when a low and high input source is available.

Example Calibration Procedure

Calibrate channel 1 (CH1) using the two-point calibration method. Set the calibration mode display to [111].

The low input source is applied to the meter when setting the zero value.

The high input source is applied to the meter when setting the span value.

From Step 6

Step 9

START HERE

Step 2

Step 3

Step 4

Step 6

Page 14

[CAL] - Calibration Modes for Input and Output continued [CAL] - Calibration Modes for Input and Output continued

Input Signal Filtering and Averaging Input signal filtering and averaging is configured in the calibration mode. Programmable averaging allows you to program the number of samples you want to average the input signal over (from 1 to 255 samples).

A programmable averaging window provides a quick response time to large input signal changes. The averaging window can be set to between 1 and 65535 counts.

Example Procedure:

Select an averaging sampling rate of 10 samples and an averaging window of 1000 counts for Channel 1 by setting [CAL] to [221].

See Advanced Calibration & On Demand Mode Supplement

(NZ203) for further calibration procedures.

START HERE

INPUT SIGNAL

FILTERING &

AVERAGING

Step 1

Step 2

From Step 6

Step 9

Step 10

Step 3

Step 4

Step 5

Example

Step 6

Example

Step

Page 15

Initial Setup Procedures [CodE_1] - Display Configuration

All digital display configuration modes, except the display brightness mode, are configured in Code 1.

All bargraph display configuration modes are configured in Code 10 (See diagram below).

See Code 1 diagram on Page 23 for a breakdown of 1st, 2nd, and 3rd digit settings.

See Code 10 diagram on Page 24 for a breakdown of 1st, 2nd, and 3rd digit settings.

CODE 1 Digital Display Configuration

CODE 10 Bargraph Display Configuration

CODE 1 Digital Display Configuration

Setpoint Annunciators Mode

The setpoint annunciators mode is configured by changing the first digit in Code 1. The setpoint annunciators can be configured to operate as follows:

On when the setpoint activates.

All annunciators are permanently on and each one only goes

off when its setpoint activates.

All annunciators are always off (See Note 1 on Code 1 diagram

on Page 20).

Setpoint 1 annunciator comes on indicating a rising signal.

Setpoint 2 annunciator comes on indicating a falling signal.

Example Procedure. The example procedure on Page 25 shows how to select the setpoint annunciators to come ON when the setpoints are OFF (not active).

Update Display at Selected Sample Rate The meters default display update rate is 0.5 seconds and is

Page 16

set in the second digit of Code 1 as [X0X].

The display can be configured to update at the input signal sample rate selected in Code 2.

Example Procedure. The example procedure on Page 25 shows how to configure the display to update at 50 samples per second by setting Code 1 to [X2X].

For these settings to take effect, the analog sample rate must be set at [2XX] in Code 2. See Code 2 Channel 1 Measurement Task and Sampling Rate on Page 29 for an example.

Manual Loader Mode

The meter can be configured to function exclusively as a manual loader by setting Code 1 to [X1X].

See Analog Output Module Supplement (NZ200) for full details on manual loader mode functions.

Display Functions Mode

The display functions mode is configured by changing the 2nd and 3rd digits in Code 1:

Selecting [X5X] enters the Data Source sub-menu.

Selecting [X6X] enters the Display Format sub-menu.

Selecting [X7X] enters the Last Digit Text Character sub-menu.

Data Source 2nd Digit [X5X] The digital display is the primary display. The bargraph display is the secondary display.

To select the data source for the primary display select 5 in the 2nd digit and 0 in the 3rd digit [X50].

To select the data source for the secondary display select 5 in the 2nd digit and 1 in the 3rd digit [X51].

Selecting 5 in the 2nd digit enters a sub-menu and allows the data from one of a number of meter registers to be selected as the data source for the displays or functions selected in the third digit.

Example Procedure. The example procedure on Page 22 shows how to select the data source for the primary display.

The three digits are set to [X50]. The same example can be used for selecting the data source for the secondary display (bargraph). The three digits are set to [X51].

The 2nd digit in Code 1 can also be used to select the data source for the remaining functions in the 3rd digit:

[X53] = Peak and Valley.

[X54] = Analog Output 1.

[X55] = Analog Output 2.

[X56] = Totalizer 1.

[X57] = Totalizer 2.

Display Format 2nd Digit [X6X] Selecting 6 in the 2nd digit enters the Display Format submenu where the following display format settings can all be configured:

Last digit rounding.

Display units (Decimal, octal, or optional 12 or 24-hour clock).

Decimal point placement.

Example Procedure. The example procedure on Page 23 shows how to configure the three display format modes for the 3rd digit selection.

Initial Setup Procedures [CodE_1] - Display Configuration continued

Text Character 2nd Digit [X7X] Selecting 7 in the 2nd digit allows you to select one of 54 characters and apply it to the last digit when the meter is in the operational display.

For example, if the meter was measuring a temperature, the display could be configured to display the reading with a C or an F in the last digit for C or F.

Example Procedure. The example procedure on Page 24 shows how to configure the last digit text character as C for centigrade (C) for the 3rd digit selection.

Note:

After setting any or all the above three modes [X5X], [X6X], [X7X], the Code 1 display must be set back to [X0X] to leave Code 1 and carry on programming.

CODE 10 Bargraph Display Configuration Set Up Bargraph Colors This mode is where the colors of the bargraph relative to the setpoints are set. Tri-color bargraphs use the following three colors:

Green.

Orange.

Red.

The bargraph colors are not applied to specific setpoints. They are applied to whichever setpoint is configured at the lowest setting, and then to each next highest setpoint in turn.

Only one color is displayed on the bargraph at any time. As the signal changes, the color selected for the most recently activated setpoint displays

Only setpoints with the same source data as the bargraph are displayed.

If all six setpoints are used the colors are set as follows:

Color 1. Color BELOW lowest setpoint.

This is the bargraph color before it

reaches a setpoint.

Color 2. Color ABOVE lowest setpoint

and BELOW the next highest.

Color 3. Color ABOVE the 2nd lowest setpoint and BELOW the next highest.

Color 4. Color ABOVE the 3rd lowest setpoint and BELOW the next highest.

Color 5. Color ABOVE the 4th lowest setpoint and BELOW the next highest.

Color 6. Color ABOVE the 5th lowest setpoint and BELOW the next highest.

Color 7. Color ABOVE the highest set-

point.

Example of

Bargraph Colors

Any one of the colors (green, orange, red, or OFF meaning no color) can be applied to each color setting (See Example:

Bargraph Colors diagram above). Selecting 2 in the 1st digit enters the Set Up Bargraph Colors mode. Selections for the 2nd and 3rd digits are not relevant at this point.

Example Procedure. The example procedure on Page 26 shows how to configure the bargraph colors.

Set Up Bargraph Scaling This mode is where the span range of the bargraph is scaled.

The span range of the bargraph can be set between 19999 to

99999 counts. There are three methods of scaling the bargraph:

Linear.

Via Linearization Table 1.

Logarithmic.

Selecting 3 in the 1st digit enters the Set Up Bargraph Scaling mode.

Linear Bargraph Scaling

The most common method of scaling the bargraph is through the Linear Bargraph Scaling sub-menu. In this menu the bar low, bar high, and bar nominal settings are set.

Bar Low [bAr_L] is the setting in counts required at the bottom of the bargraph.

Bar High [bAr_h] is the setting in counts required at the top of

the bargraph.

Bar Nominal sets the point on the bargraph at which the bar begins to light up. This can be any position between and including the bar low and bar high settings.

If bar nominal is set to the bar low setting, the bargraph behaves like a typical bargraph making the segments light up from the bottom of the bar and grow towards the top.

If bar nominal is set to the bar high setting, this makes all segments from the displayed signal to the top of the bar light up. As the signal increases, the number of lit segments between the signal and the bar high setting becomes steadily less. When the signal reaches the bar high setting no segments are lit.

Bargraph Nominal Set Low or High

Setting bar nominal to the midpoint between bar low and bar high makes the bargraph behave like a typical center zero bargraph. This means the bargraph lights up at the center of the bar and moves either up or down the bar depending on the displayed signal.

For example, if the meter's full scale range is 20,000 counts, the midpoint is 10,000 counts. If a signal of 10,000 counts is applied, only one segment at the 10,000 count mark lights up. If a signal of 17,000 counts is applied, the segments between the center segment (10,000 counts) and the 17,000 count mark light up.

If a signal of 5000 counts is applied, the segments between the center segment (10,000 counts) and the 5000 count mark light up.

Typical Center Zero Bargraph

An added feature of this bargraph is that it can also be non-symmetrical. This means that the bar nominal setting does not need to be set at the mid-point between bar low and bar high. For example, if the bargraph is configured to display 200 to 800 C, bar low is set to 200 counts and bar high is set to

800 counts. Bar nominal is set to 0 counts. If a signal of 50 C is applied, the bar lights from 0 down to 50. If a signal of 600 C is applied, the bar lights from 0 up to 600.

Page 17

Initial Setup Procedures [CodE_1] - Display Configuration continued

Example Procedure. The example procedure on Page 27 shows how to scale the bargraph using linear scaling.

Non-symmetrical Zero

Bargraph

Bargraph Scaling using Linearization Table 1 When set in this mode, the register selected to be displayed on the bargraph display (Code 1 set to [XX1]) is first processed through a 32-point flexible linearization table (Table 1) before being displayed.

This can be used, for example, if channel 1 is the required digital display while the bargraph display is the square root of channel 1.

See Linearization Supplement (NZ207) for full details to set up linearization Table 1.

Selecting 3 in the 1st digit and 1 in the 3rd digit selects Bargraph scaling via Linearization Table 1.

Example Procedure. To scale the bargraph using Linearization Table 1, follow the Scale Bargraph using Linear Scaling Procedure on Page 27. Ensure the secondary (bargraph) display has been set up in Code 1 and Linearization Table 1 has been formatted and selected for the required application.

Logarithmic Bargraph Scaling

Logarithmic scales are used in a wide variety of measurements.

Probably the most well known logarithmic scale is the Richter scale for measuring earthquakes. Other log scales used include sound level (dB), radio frequency signals, power levels (dBm), and numerous radiation signals.

In all logarithmic scales a reference level is required that is the level at 0 dB. For example, in an RF measurement 0 dBm is at a reference of 1 mW.

The scale is calculated from:

10 log10

counts (input)

reference

If the meter is scaled so that:

1 mW = 100 counts and 1 W = 100,000 counts Then the reference for 0 dBm would be set to 100 counts:

(input)

100

10 log10

Decade

(Counts)

100

1000

10,000

100,000

1,000,000

= 0 dBm

dBm

20

10

Now every 10 dBm represents a decade, the bargraph can be scaled to a different amount of bars per decade (as set in the 3rd digit).

Page 18

Example of Bars per Decade

Reference. This is the number of counts displayed for a 0 dB reference. Range: 1 to 99999 counts.

Bar Nominal. See Bar Nominal description under heading:

Linear Bargraph Scaling.

Selecting 3 in the 1st digit and 3, 4, 5, 6, or 7 in the 3rd digit enters the Set Up Scaling for Logarithmic Bargraph sub-menu:

Selecting 3 in the 3rd digit sets the log to 10 Bar/Decade.

Selecting 4 in the 3rd digit sets the log to 20 Bar/Decade.

Selecting 5 in the 3rd digit sets the log to 25 Bar/Decade.

Selecting 6 in the 3rd digit sets the log to 33 Bar/Decade.

Selecting 7 in the 3rd digit sets the log to 50 Bar/Decade.

Example Procedure. The example procedure on Page 28 shows how to scale the bargraph using example logarithmic settings.

Bargraph Display Format

After the bargraph colors have been set and the bargraph scaled, the display format can be set. This is normally the final setting. The 2nd digit selects the format of the bargraph display.

There are four display format settings available:

Setpoints on Bar. Selecting [X0X] means that the setpoints are displayed on the bar as lit segments in the current display color.

When the display color changes, the setpoint segments change to that color. When the bargraph lights up on or beyond a setpoint, the setpoint segment goes out.

Example of Setpoints on Bargraph

Peak and Valley on Bar. Selecting [X1X] means that peak and valley are displayed as lit segments and are updated as they change. The setpoints are not displayed.

Min/Max with Setpoints. Selecting [X4X] means that the segments of the bar remain lit over the minimum and maximum signal variations. The setpoints are displayed as lit segments.

This is a useful mode for seeing process varia-

tions at a glance.

Note:

When moving from another display format to the Min/Max with Setpoints mode, the peak and valley settings must be set to the current settings by entering the Peak View mode or Valley View mode and pressing the UP and DOWN buttons at the same time.

Example:

Peak and

Valley on

Bargraph

When moving from Min/Max with Setpoints mode to another display format, the bar nominal [bAr_n] setting must be reset to its original settings in Code 10 [3XX].

Bar Only. Selecting [X7X] means that only the bargraph display signal is displayed on the bar.

Setpoints and peak and valley are not displayed.

Example: MIN and MAX on Bargraph

Initial Setup Procedures [CodE_1] - Display Configuration continued

Page 19

Initial Setup Procedures [CodE_1] - Display Configuration continued

Page 20

Initial Setup Procedures [CodE_1] - Display Configuration continued

Configure Data Source Procedure The following example procedure describes how to select the source of the data to be displayed for the third digit selection.

Example Procedure:

Configure the Primary Display with the display [diSP] as the data source by setting Code 1 to [X50]. See diagram at the bottom of the page for data source selection options.

START HERE

CONFIGURE

DATA SOURCE

Step 2

From Step 5

Step 7

Programming Tip

Step 8

Example

Step 3

Step 4

Step 5

Step 9

Page 21

Initial Setup Procedures [CodE_1] - Display Configuration continued

Configure Display Format Mode Procedure

The following example procedure describes how to configure the display format mode for the third digit selection and covers:

Last Digit Rounding.

Display Units.

Decimal Point Placement.

Example Procedure:

Configure the display format mode for channel 1 with rounding by 2s, decimal display units, and the decimal point placed between display digits

4 and 5 by setting Code 1 to [X61] to enter the Display Format Mode.

START HERE

CONFIGURE

DISPLAY

FORMAT

Step 2

Step 3

Step 4

From Step 5

Step 6

Example

Step 7

Step 8

Step 9

Step 5

Page 22

Initial Setup Procedures [CodE_1] - Display Configuration continued

Configure Last Digit Text Character Procedure

The following example procedure describes how to select the last digit text character.

Example Procedure:

Configure Channel 1 with C as its last digit text character (for C) by setting Code 1 to [X71] to enter the Select Last Digit Text Character Mode. See diagram opposite.

START HERE

CONFIGURE

LAST DIGIT

TEXT CHARACTER

Step 1

Step 2

Step 3

From Step 6

Step 7

Step 4

Step 5

Step 6

Step 8

Step 9

Step

Example

Page 23

Initial Setup Procedures [CodE_1] - Display Configuration continued

Configure Setpoint Annunciators Procedure

Configure Update at Sample Rate Procedure

The following example procedure describes how to configure setpoint annunciators.

The following example procedure describes how to configure the display to update at the sample rate selected in Code 2.

Example Procedure:

Configure the setpoint annunciators to come ON when the setpoints are OFF (not active) by setting Code 1 to [1XX].

Example Procedure:

UPDATE AT SAMPLE RATE PROCEDURE Update the display at the sample rate selected in Code 2 [2XX] by setting Code 1 to [X2X].

START HERE

Step 1

Step 2

START HERE

Step 1

Step 2

Step 3

Step 4

Step 3

Step 4

X X

Step 5

Programming Tip

The Configuring Setpoint

Annunciators and the Update at Sample Rate procedures can be combined so that Code 1 could be set to [12X] (for the above examples) in a single procedure.

Page 24

Initial Setup Procedures [CodE_1] - Display Configuration continued

Configure Bargraph Colors Procedure

START HERE

CONFIGURE

BARGRAPH

COLORS

Step 1

Step 2

Step 3

Step 4

Step 5

From Step 6

Step 7

Step 8

Step 9

Step 10

Step 6

Step

Page 25

Initial Setup Procedures [CodE_1] - Display Configuration continued

Scale Bargraph using Linear Scaling Procedure

START HERE

Step 1

Step 2

Step 3

Step 4

Step 5

Step 6

Page 26

From Step 6

Step 7

Step 8

Step 9

Step 10

Step 11

Step

Initial Setup Procedures [CodE_1] - Display Configuration continued

Scale Bargraph using Logarithmic Scaling Procedure

From Step 6

Step 7

START HERE

Step 1

Step 2

Step 3

Step 4

Step 5

Step 6

Step

Step 8

Step 9

Step 10

Page 27

Initial Setup Procedures [CodE_2] - Channel 1 Measurement Task & Sampling Rate

The Tiger 320 Series meter can be configured to measure almost any input signal. The measurement task and sampling rate for Channel 1

(CH1) is configured in the three digits of Code 2. The diagram below lists the available configuration selections in Code 2.

Example Procedure:

Configure CH1 for a voltage input with 10 samples/second (60 Hz rejection) sampling rate and output rate of 0.1 seconds by setting Code 2 to [000].

START HERE

CONFIGURE CH1

MEASUREMENT

TASK & SAMPLING

RATE

Step 2

Step 3

Step 4

Save setting and

enter Code 3

Example

Page 28

Step 5

Step

Initial Setup Procedures [CodE_3] - Channel 1 Post Processing & Serial Mode Functions

Post processing functions refer to functions that occur to the input after it has been configured and scaled.

Example Procedure:

Configure the meter to apply square root to the CH1 signal by setting Code 3 to [100].

Post processing for Channel

1 (CH1) is configured in the first digit of Code 3. The diagram below lists the available post processing configuration

selections in Code 3 (1st digit only).

START HERE

CONFIGURE CH1

POST PROCESSING

FUNCTIONS

Step 1

Step 2

Step 3

Step

Print Mode Data Printing Direct to Serial Printer Print mode data logging is a simple method of capturing data using the meters print mode. The data can be printed directly to a serial printer from the meter.

The print mode uses the meters serial communications port to connect to a remote serial printer. The data can be printed with or without a Day: Month: Year or Hours: Minutes: Seconds time stamp.

From Step 3

Step 4

Step 5

Programming tip

For full details on the Serial Mode, see Serial Communications Output Module supplement.

Print Mode Data Printed Direct to PC The print mode can also be used to print data to a PC where it is logged in a Windows Terminal program.

The print mode uses the meters serial communications port to connect to the PC. The data can be logged with or without a Day: Month: Year or Hours: Minutes: Seconds time stamp.

Time stamp settings are configured in Code 8.

Time stamp settings are configured in Code 8.

Page 29

Initial Setup Procedures [CodE_4] - Channel 2 Measurement Task & Sampling Rate

Code 4 is a single code that combines all the configuration and post processing functions available for Channel 2.

When a dual input signal conditioner is installed, the second input signal is processed and displayed on CH2.

Measurement task and 32-point linearization for CH2 is configured in the 1st and 2nd digits of Code 4. The diagram opposite lists the available configuration selections in Code 4.

Example Procedure:

Configure CH2 for a direct voltage input with no linearization by setting Code 4 to [010].

See I-Series Input Modules Guide (Z87) for procedures to set up a dual input module.

START HERE

CONFIGURE CH2

MEASUREMENT

TASK

Step 1

Step 2

Step 3

Page 30

From Step 3

Step 4

Step 5

Step

Initial Setup Procedures [CodE_5] - Channel 3 Functions

Code 5 is a single code that combines all the configuration and post processing functions available for Channel 3.

When a triple input signal conditioner is installed, the third input signal is processed and displayed on CH3.

Post processing and measurement task functions for CH3 are configured in the 1st, 2nd, and 3rd digits of Code 5. The diagram opposite lists the available configuration selections in Code 5.

Example Procedure:

Configure CH3 to display the square root of a voltage input by setting Code 5 to [11X].

See I-Series Input Modules Guide (Z87) for procedures to set up a triple input module.

START HERE

CONFIGURE

CH3 FUNCTIONS

Step 1

Step 2

Step 3

Step

Step 4

From Step 4

Step 5

Page 31

Initial Setup Procedures [CodE_6] - Channel 4 Functions

Code 6 is a single code that combines all the configuration and post processing functions available for Channel 4.

When a quad input signal conditioner is installed, the fourth input signal is processed and displayed on CH4.

Post processing and measurement task functions for CH4 are configured in the 1st, 2nd, and 3rd digits of Code 6. The diagram opposite lists the available configuration selections in Code 6.

Example Procedure:

Configure CH4 as direct display of voltage input by setting Code 6 to [01X].

See I-Series Input Modules Guide (Z87) for procedures to set up a quad input module.

START HERE

CONFIGURE CH4

FUNCTIONS

Step 1

Step 2

Step 3

Step

Step 4

Page 32

From Step 4

Step 5

Initial Setup Procedures [CodE_7] - Result Processing

The third digit of Code 7 performs various math functions between channel 1 and channel

2 and stores this data in the result register.

The data in the result register can then be further processed by the selections made in the 1st and 2nd digits.

Example Procedure:

Configure Code 7 to add the input of CH1 and CH2 and directly display the result by setting Code 7 to [003].

See I-Series Input Modules Guide (Z87) for procedures to set up a dual, triple, or quad input module.

Linearization Table Notes

START HERE

CONFIGURE

RESULT

PROCESSING

Step 2

Step 3

Step

Step 4

From Step 4

Step 5

Page 33

Initial Setup Procedures [CodE_8] - Data Logging & Print Mode

Up to 4000 samples can be logged within the meter in the cyclic or linear FIFO mode and saved for later downloading to a PC, using a terminal emulation program, or printing directly to a serial printer.

Data logging can be triggered (activated) from a setpoint, the program button, or from an external switch. See the 3rd digit in the diagram below.

Data from up to four selectable registers can be logged with one of the following printer or spreadsheet style time and date stamps. All time and date stamps are generated from an optional real-time clock (see the 2nd digit in the diagram below):

No time stamp.

Month - Day - Year. Hours:Minutes:Seconds.

Day - Month - Year. Hours:Minutes:Seconds.

Hours:Minutes:Seconds.

Printer style time and date stamps have a carriage return and line feed. Spreadsheet style time and date stamps are continuous on a single line.

See Serial Communications Module Supplement (NZ202) for full details on the Data Logging and Print Mode Options.

Initial Setup Procedures [CodE_9] - Functions for Digital Input Pins

The TEST, HOLD, and LOCK pins are located at the rear of the meter to accommodate external switched digital inputs.

When switched to the COMMON pin, they can be programmed in Code 9 to perform remote resetting functions to add to the functionality of the meter.

Note:

CAPTURE, HOLD, and LOCK pins can be a setpoint activation source. See Setpoint Programming mode.

Page 34

Setpoint Programming Mode

All setpoint activation and control settings are selected and configured using the front panel buttons in the setpoint programming mode. Or, software configured via the meter configuration utility program if the meter is connected to a PC through the serial port. The meter has six software driven setpoints, independently configured to operate within the total span range of the meter and the selected input module.

Setpoint Programming Mode

See the Setpoint Programming Mode Logic Diagram opposite.

The setpoint programming mode is entered by pressing the meters P and

buttons at the same time.

Setpoint Activation Values

Each setpoint activation value is individually programmed. Setpoint activation values can be set within the total span range of the meter and the selected input module.

Setpoint and Relay Control Settings See the Setpoint and Relay Control Settings diagram on Pages 41 and 42.

To enter press P and buttons at the same time Setpoint Programming Mode

Setpoint Activation Values

Enter these menus to set setpoint

(SP) activation values

[SP_1]

Setpoint 1 Default Setting = 18000

[SP_2]

Setpoint 2 Default Setting = 18000

[SP_3]

Setpoint 3 Default Setting = 5000

The control settings provide access to the following setpoint and relay functions for configuration using the meters 1st, 2nd, and 3rd digits:

1st Digit Relay Energize Functions.

2nd Digit Setpoint Activation Source.

3rd Digit Setpoint Delay, Timer, and Reset and Trigger Functions.

[SP_4]

Setpoint 4 Default Setting = 5000

[SP_5]

Setpoint 5 Default Setting = 10000

[SP_6]

Setpoint 6 Default Setting = 10000

Setpoint & Relay Control Function Settings

Enter these menus to configure SP control values

[SPC_1]

Setpoint 1

[SPC_2]

Setpoint 2

[SPC_3]

Setpoint 3

[SPC_4]

Setpoint 4

[SPC_5]

Setpoint 5

[SPC_6]

Setpoint 6

Setpoint Programming Mode Logic Diagram

Page 35

Setpoint Programming Mode continued

Relay Energize Functions

All setpoints activate at the setpoint value.

All relays/setpoints are programmable to energize above or below the setpoint value.

Setpoint Activation Source

Setpoints activate from any input channel, selected meter register, or external switched inputs (digital input pins).

Setpoint Latching

Setpoints can be programmed in relay latching modes.

Setpoint Reset & Trigger Setpoints can be programmed to reset selected registers, or be manually reset. They can also trigger a data print or a data log.

SP-B

SP-A

Setpoint Tracking

Setpoint tracking can

be applied to setpoints configured in the hysteresis, deviation, or PID modes.

Display Flashing

Display flashing can be applied to setpoints configured in the hysteresis or deviation modes.

Each setpoint can be programmed to make the display flash on and off while the setpoint is active, and keep it flashing until the setpoint de-activates.

Real-time Clock Option

Any setpoint can be programmed to operate from the real-time clock option.

Data Logging

Any setpoint can be programmed to log data within the meter (up to

4000 samples).

Data Printing to Serial Printer Any setpoint can be programmed to send data directly to a serial printer.

Data Printing to PC Any setpoint can be programmed to send data directly to a connected PC.

Hysteresis or Deviation

Each relay can operate in a hysteresis or deviation mode.

Page 36

PID Control Settings

The PID (proportional, integral, derivative) control function provides exceptional control stability during control process applica-

tions. PID control is available from the following outputs:

Setpoint / relay output.

Analog output.

Relay and analog output at the same time.

PID control from the setpoint / relay output is available from SP1 and SP2 only.

There are two PID control outputs available via the analog output:

PID1 stored in register 50.

PID2 stored in register 51.

PID Control

Timer Modes

Each setpoint can be programmed to operate the relay in one of the following seven resident timer modes:

Normal Mode Timer

Single actuation, delay-on-make (DOM) and delay-onbreak (DOB).

Normally OFF/Pulsed ON Timers

Repeat ON Mode Timer multiple actuation, programma-

ble offand on-time.

Pulse ON Mode Timer single actuation, programmable

DOM and maximum on-time.

1-Shot ON Mode Timer single actuation, programmable

DOM and minimum on-time.

Normally ON/Pulsed OFF Timers Repeat OFF Mode Timer multiple actuation, program-

mable offand on-time.

Pulse OFF Mode Timer single actuation, programmable

DOB and maximum off-time.

1-Shot OFF Mode Timer single actuation, programmable

DOB and minimum off-time.

Hysteresis or Deviation

Each setpoint can be individually programmed to energize the relay in the hysteresis or deviation mode, with or without initial startup inhibit.

Hysteresis (deadband) is the programmable band above and below the setpoint value that determines when and for how long the relay is energized or de-energized. The setpoint can be programmed to energize the relay above or below the setpoint value.

The hysteresis setting can be any value between 0 and 65535 counts. The number of counts selected act both positively and negatively on the setpoint, forming a hysteresis band around the setpoint.

For example, if the setpoint setting is 500 counts and the hysteresis setting is 10 counts, the hysteresis band around the setpoint setting is 20 counts, starting at 490 counts and ending at 510 counts.

Note:

If hysteresis is set with ZERO counts, the relay energizes AT or ABOVE the setpoint value.

Setpoint Programming Mode continued Setpoint Programming Mode continued

Deviation (passband) is the programmable band around the setpoint in which the setpoint can be programmed to energize the relay inside or outside the deviation band.

The deviation setting can be any value between 1 and 65535 counts. The number of counts selected act both positively and negatively on the setpoint, forming a deviation band around the setpoint.

For example, if the setpoint setting is 1000 counts and the deviation setting is 35 counts, the deviation band around the setpoint setting is

70 counts starting at 965 counts and ending at 1035 counts.

Normally OFF / Pulsed ON Modes These are delay modes were the relay is normally off and pulses on when the setpoint activates.

Repeat ON Mode

Multiple actuation, programmable on and off time settings.

Repeat ON Mode

SP ON

Deviation

Initial Start-up Inhibit.

On power-on, start-up inhibit prevents the relay from energizing on the first setpoint activation cycle. Depending on how the meter has been programmed, initial start-up inhibit either functions during a falling input signal, or during a rising input signal.

Relay Time Control Modes The following time control mode settings can cover almost every relay timer application.

All setpoints can be individually programmed to operate a relay in one of the following time control modes above or below the setpoint value.

Hytseresis

Normal Mode

This mode individually programs a relays setpoint with delayon-make (DOM) and delay-on-break (DOB) settings.

Normal Mode

SP ON

SP OFF

RLY ON

RLY OFF

Adj.

DOM

Adj.

DOB

SP OFF

RLY ON

RLY OFF

Adj.

ON-T

Adj.

OFF-T

Adj.

ON-T

Pulse ON mode (Programmable ON-time) Pulse ON Mode (Prog. Max ON-time) Single actuation, programmable DOM and on time settings.

SP ON

SP OFF

RLY ON

RLY OFF

Adj.

MAX

ON-T

Adj.

DOM

1-Shot ON mode (Programmable Minimum ON-time)

Single actuation, programmable DOM and minimum on time settings.

1-Shot ON Mode (Prog. Min. ON-time) SP ON

SP OFF

RLY ON

RLY OFF

Adj.

DOM

Adj.

MIN ON-T

Page 37

Setpoint Programming Mode continued

Normally ON / Pulsed OFF Modes These are delay modes were the relay is normally on and pulses off when the setpoint activates.

1-Shot OFF mode (Programmable Minimum OFF-time)

Single actuation, programmable minimum off time and DOB settings.

1-Shot OFF Mode (Prog. Min. OFF-time) SP ON

SP OFF

RLY ON

RLY OFF

Adj.

DOB

Adj.

MIN OFF-T

Pulse OFF mode (Programmable OFF-time) Pulse OFF Mode (Prog. MAX OFF-time) Single actuation, programmable off time and DOB.

SP ON

SP OFF

RLY ON

RLY OFF

Adj.

DOB

Adj.

MAX

OFF-T

Level 1

Setpoint & Relay Basic Mode

This is an easily programmable mode for users who require the

following basic setpoint and relay functions:

First Digit Relay Energize Functions

Relays programmed to energize above or below the

setpoint value.

Second Digit SP Activation Source

Setpoints programmed to activate from selectable meter registers or one of six external switched inputs.

Third Digit Setpoint Latching

Relays programmed with latching and manual reset

options.

Level 2

Setpoint & Relay Intermediate Mode

Level 2 uses all Level 1 functions and is further extended by the following programmable modes. The functionality of the relay energize functions are extended by allowing the relays to be programmed with or without initial start-up inhibit.

Hysteresis, Deviation & PID Mode

This mode adds extra functionality to the basic mode by providing programmable hysteresis or deviation settings for all setpoints, or PID control from setpoints SP1 and SP2.

Timer Modes

These modes add even more functionality to the basic and intermediate mode by providing each setpoint with a choice of one of seven resident programmable timers.

Level 3

Setpoint & Relay Advanced Mode

Repeat OFF Mode

Multiple actuation, programmable off and on time settings.

Repeat OFF Mode

SP ON

Level 3 uses all Level 1 and Level 2 functions combined with reset and trigger functions to provide an extremely powerful advanced mode.

Level 3 enables you to program all setpoints individually for operations normally requiring sophisticated controllers.

SP OFF

RLY ON

RLY OFF

Adj.

OFF-T

Adj.

ON-T

Adj.

OFF-T

Each setpoint can be individually configured for basic to advanced operations in the following three levels. Each operational level is designed to provide only the required relevant setpoint and relay functions.

The modes at Level 2 and Level 3 can be set to OFF for each individual setpoint, ensuring that no other functions are programmed to influence the setup.

Page 38

Setpoint Programming Mode continued Setpoint Programming Mode continued

Level 1 - Basic Mode - Programming Procedures

Example Procedure:

The following procedure describes how to program setpoint

1 (SP1) for the following Level 1 setpoint and relay functions:

SP1 to activate from Channel 1 (CH1).

LEVEL 1 SETPOINT CONFIGURATION

Relay to energize above or below SP1 value.

Relay to latch with manual relay reset.

See Setpoints and Relays Supplement (NZ201) for procedures to program all setpoint and relay operational levels (Level 1 to Level 3).

START HERE

Step 1

Step 2

Step 3

Step 4

From Step 5

Step 6

Step 7

Step 8

Step 9

Step 5

Step 10

Programming tip

All required setpoint activation values (SP1 to SP6) can be adjusted before programming setpoint and relay control function settings. See Setpoint Programming Mode Logic Diagram on Page 41.

Page 39

Setpoint Programming Mode continued Setpoint Programming Mode continued

Setpoint & Relay Control Settings Diagram

The diagram below and continued on Page 42 shows the 1st, 2nd, and 3rd digit control settings for the setpoints and relays.

Programming Tip

PXX

Page 40

Setpoint Programming Mode continued Setpoint Programming Mode continued

Programming Tip

PXX

Programming Tip

Page 41

Registers That Can Be Selected By Front Panel Push Button Programming

A Tiger 320 Series meter has 6,144 registers which are provided for use by the operating system and the powerful Custom Macro Programming system.

40 Manually Selectable Registers Using the front panel buttons, there are 40 registers that may be selected for use within the following functions:

[CodE_1] - Display Configuration [X50]. Selection of a register as the data source for displays, peak and valley, totalizers and analog outputs. (See pages 20 & 22)

Setpoint Control Settings [X1X]. Selection of a register

as the data source for a setpoint. (See Page 41)

Setpoint Control Settings [XX7]. Selection of a destination register that is to be reset by a setpoint with the contents of a selected source register. (See Page 42)

Setpoint Control Settings [XX7]. Select which registers contents are to be copied into the destination register by a setpoint. (See Page 42)

The 40 registers that can be selected as a data source, a reset source or a reset destination for the functions above are shown in the table on the right.

The table shows, in seven columns, the functions where these registers can be used.

Where a register is more likely to be used in a particular function, a closed circle is shown in the column. For those functions where a register is less likely to be used, an open circle is s hown.

No register number is shown for the first 11 functions, because these 11 functions are identified in the display menu for direct selection by their code names.

When cycling through the Registers Menu and then Registers 1 to 244, the numerical Register Set will increment through each decade in turn, from 1 to 0, while the button is held down. When [200] is reached, [oFF] or [tArE] will be displayed. To select a specific number set, the button should be released and pressed again each time the left most decade displays the desired number for that decade.

To quickly exit the numerical 1 to 244 Register Set, hold the button down while cycling through the decades, and release it when [oFF] or [tArE] appears.

Registers that Should Not be Used The following registers are contained within the selectable

1 to 244 Register Set, but they should not be selected because they are either reserved for future use, or for use by the operating system only:

15, 38, 47-48, 52-53, 61-64, 123-128, 140-141, 234-244

Any selection of these Registers may cause a malfunction.

Page 42

Resetting and Incrementing Using Setpoints Setpoints may be used to reset and/or increment registers. In the example shown below, 2 liter soft drink bottles are being filled and packed 12 to a case. Using the setpoint reset and increment feature, the number of bottles and the total number of filled cases is easily calculated and displayed. Totalizer 1 counts from 0 to 2, resets, and repeats. CH 2 counts from 0 to 12, resets, and repeats.

USING SETPOINTS TO INCREMENT AND RESET REGISTERS

Functional Diagram

AC Neutral, DC AC Line, + DC AC/DC Power Input

Connector Pinouts Connector Pinouts

Rear Panel Pinout Diagram

Input Signal Pins 1 to 6 See the I-Series Input Signal Modules Guide (Z87) for connection details of all input modules. On most single input signal conditioners, usually Pin 1 is the signal high pin (Hi +) and Pin

3 is the signal low pin (Lo ).

Function Pins Pins 17 to 21 Pin 17 Program Lock. By connecting the PROGRAM LOCK pin to the COMMON pin (pin 11 on the main PCB), the PROGRAM LOCK pin allows the meter's programmed parameters to be viewed but not changed.

Pin 18 Hold Reading. By connecting the HOLD READING pin to the COMMON pin (pin 11), the HOLD READING pin allows the meter's display to be frozen. However, A/D conversions continue

and as soon as pin 9 is disconnected from pin 11 the updated reading is instantly displayed.

Pin 19 Display Test and Reset. The DISPLAY TEST and RESET pin provides a test of the meter's display and resets the microprocessor when the DISPLAY TEST and RESET pin is connected to the COMMON pin (pin 11).

Pin 20 Common. To activate the HOLD, TEST and RESET, or LOCKOUT pins from the rear of the meter, the respective pins have to be connected to the COMMON pin.

Pin 21 Capture. Connecting the CAPTURE pin (pin 21) to the COMMON pin (pin 11), allows a selected relay to be activated.

Chassis Ground Tab. Only on versions with metal sheath casing.

Page 43

Carrier Board Output Pins

Analog Output

Pins 25 to 27 Analog Output Pins. The analog output pins are:

Pin 25 Positive (+) analog output 1.

Pin 26 Negative () analog output 1 and 2.

Pin 27 Positive (+) analog output 2.

SSR Output

Pins 28 to 31 SSR Output Pins.

Pin 28 Normally open 6 (SP6) 210 mA, 300 VDC SSR.

Pin 29 Common 6 (SP6).

Pin 30 Normally open 5 (SP5) 210 mA, 300 VDC SSR.

Pin 31 Common 5 (SP5).

Serial Outputs RS-232 or RS-485 Pins 32 37 Serial Comm. Pinouts for RS-232 & RS-485.

Relay Options

The meter has relay options on the main / processor board.

The main / processor board supports up to four electromechanical relays. Combined they provide 16 options ranging from a single 4 A Form A relay up to a maximum of two 4 A Form A and two 9 A Form C.

Electromechanical Relays

The main / processor board supports relay combination options using up to four electromechanical relays.

A maximum of two 4 A Form A and two 9 A Form C relays. Relay outputs for one to four setpoints can be ordered for factory installation on the main board in any required combination of up to two 9A form C and two 4A form A relays.

Main / Processor Board

Page 44

Component Layout and External Devices

Modular Construction

The Tiger 320 Series of 32-bit Programmable Meter Controllers incorporates, in one instrument, all the different functions required by todays automation and process control applications. This is made possible by modular construction, around standard case sizes, built to American, European, and Japanese standards.

The range comes with a wide variety of display options, including 5 or 6-digit numeric or alphanumeric displays, 6-digit LCD displays, and 51 or 101-segment red, green, or tri-color straight and circular bargraphs.

All meters are housed in one of three DIN case sizes, or the popular 4 ANSI case, and provide the ideal solution for your measurement and process control applications.

Modular construction ensures you dont have to pay for unnecessary hardware. Simply order the input and output options to suit your application.

Tiger 320 Series Modular Construction

Output

Carrier

Board

Display Driver

Board

Digital

Display

AC / DC

Power Pins

14, 15

Standard Serial

Output Module

(RS-232 or RS-485)

Analog

Output

Module

Input Signal

Conditioner

Pins 1-6

Input Signal

Conditioner

Main/Processor

Board

Bargraph

Display

Display

Board

Exploded View of Meter Modular Boards

Page 45

Component Layout and External Devices continued

Input Signal

Conditioner

PCB

Analog output Selection

Pin 1

Pin 2

Pin 14

Pin 13

Display Board

Display Driver

Board

Standard Serial Output Modules RS-232 or RS-485

Note:

Externally mounted

Ethernet compatible

communication output

modules are available

that connect directly

to the standard (RS-

232 / RS-485) serial module outputs.

RS-485 Output Module PCB

RS-232 Output Module PCB

Opto Isolated I/O Modules Connect to External DIN Rail Mounting Breakout Box

10 Digital Outputs

Add-on Board

3M IDC

Cable

Analog Output Module PCB

Current or

Voltage

Selection

Header

CURRENT

Position

VOLTAGE

Position

Available in Single (0~4-20mA or 0-10V) or Dual (0-10V & 0-10V)

DIN Rail Mounting Breakout Box with Screw Terminal Blocks

Standard 6 Digital

Inputs/6 Digital Outputs

DIN Rail

Relay Module

Page 46

Installation Guidelines

Installation

1. Install and wire meter per local applicable codes/regulations, the particular application, and good installation practices.

2. Install meter in a location that does not exceed the maximum operating temperature and that provides good air circulation.

3. Separate input/output leads from power lines to protect the meter from external noise. Input/output leads should be routed as far away as possible from contactors, control relays, transformers and other noisy components. Shielding cables for input/output leads is recommended with shield connection to earth ground near the meter preferred.

4. A circuit breaker or disconnect switch is required to disconnect power to the meter. The breaker/switch should be in close proximity to the meter and marked as the disconnecting device for the meter or meter circuit.

The circuit breaker or wall switch must be rated for the applied voltage (e.g., 120VAC or 240VAC) and current appropriate for the electrical application (e.g., 15A or 20A).

5. See Case Dimensions section for panel cutout information.

6. See Connector Pinouts section for wiring.

7. Use 28-12 AWG wiring, minimum 90 C (HH) temperature rating. Strip wire approximately 0.3 in. (7-8 mm).

8. Recommended torque on all terminal plug screws is 4.5 lb-in (0.51 N-m).

Page 47

Index

Analog Output / Analog Retransmission.......................... 12-13 Calibration of Analog Output........................................... 12 Dual (0-10V) Analog Output............................................ 12 Location of Analog Output Module................................. 45 Pinout of Analog Output.................................................. 46 Scaling of Analog Output................................................ 12-13 Select Source for Analog Output.................................... 12 Auto Zero Maintenance for Weighing Applications......... 12 Set Parameters for CH1, CH2, CH3 & CH4................... 11 Averaging - Digital Filtering............................................... 13 Set Parameters for CH1, CH2, CH3 & CH4................... 12

Block Diagram of Software & Hardware............................ 4 Brightness Display.............................................................. 11

Calibration........................................................................... 12-15

Calibration Thermocouple or RTD.................................. 12 Manual Calibration.......................................................... 14 Single-Point Calibration................................................... 14 Two-Point Calibration...................................................... 14 Case Dimensions................................................................ 50 Modular Construction...................................................... 45 Channel 1 Settings.............................................................. 28-29

32 Point Linearization...................................................... 29 Analog Input Signal Sample Rate................................... 28 Counter/Resident Timer/Clock........................................ 28 Measurement Task.......................................................... 28 Post Processing.............................................................. 29 Print Mode....................................................................... 29 Sampling Rate................................................................. 28 Serial Mode..................................................................... 29 Smart Input Module......................................................... 28 Channel 2 Settings.............................................................. 30 Channel 3 Settings.............................................................. 31 Channel 4 Settings.............................................................. 32 Channel 1 & Channel 2 Results Processing

32 Point Linearization...................................................... 33 Maths Functions.............................................................. 33 Code 1 - Display Configuration......................................... 16-27 Configure Bargraph Colors Procedure............................ 25 Configure Bargraph Using Linear Scaling Procedure..... 26 Configure Bargraph Using Logarithmic Scaling.............. 27 Configure Data Source Procedure.................................. 21 Configure Display Format Mode Procedure.................... 22 Configure Last Digit Text Char. Procedure...................... 23 Configure Setpoint Annunciators Procedure................... 24 Configure Update at Sample Rate Procedure................ 24 Data Source - 2nd Digit [X5X]......................................... 16 Display Format - 2nd Digit [X6X]..................................... 16 Display Functions Mode.................................................. 16 Manual Loader Mode...................................................... 16 Setpoint Annunciators Mode........................................... 16 Text Character - 2nd Digit [X7X]..................................... 16 Update Display at Selected Sample Rate....................... 16 Code 2 - Channel 1 Measurement Task

and Sampling Rate........................................................ 28

Code 3 - Channel 1 Post Processing

and Serial Mode Functions.......................................... 29

Code 4 - Channel 2 Measurement Task

and Sampling Rate........................................................ 30 Code 5 - Channel 3 Functions........................................... 31 Code 6 - Channel 4 Functions........................................... 32 Code 7 - Result Processing............................................... 33

Page 48

Code 8 - Data Logging & Print Mode................................ 34 Code 9 - Functions for Digital Input Pins......................... 34 Code 10 - Bargraph Display Configuration...................... 17-18 Code Blanking..................................................................... 10-11 Clock/Timer

Configuration................................................................... 28, 31, 32 Real-time Clock Configuration........................................ 28, 31, 32 Real-time Clock Date...................................................... 34 Time Stamp..................................................................... 34

Component Layout & External Devices Modular Construction...................................................... 45 Component Layout.......................................................... 46 Connections

Carrier Board Output Pinouts.......................................... 44 Connector Pinouts........................................................... 43 External Devices............................................................. 46 Rear Panel Pinout Diagram............................................ 43 Controls & Indicators......................................................... 5-6 Annunciator LEDs........................................................... 5 Down Button.................................................................... 5 Error Message................................................................. 6 LED Display..................................................................... 5 Program Button............................................................... 5 Program Lockout Switch................................................. 6 Scrolling Display Text Messaging.................................... 5 Setpoint Lockout Switch.................................................. 6 Seven Segment LED Displays........................................ 5 Up Button........................................................................ 5 Data Logging

Downloading Logged Data from Meter........................... 34 Printing Logged Data...................................................... 34 Real-time Clock............................................................... 34 Digital Input Pins................................................................ 34 Display Brightness Setting................................................ 11 Display Functions............................................................... 16-27 Bargraph Colors.............................................................. 17 Bargraph Display............................................................. 18 Data Source.................................................................... 21 Display Format and Decimals......................................... 22 Display Rounding............................................................ 22 Last Digit Text Character................................................. 23 Setpoint Annunciator Mode............................................. 24 Update at Sample Rate................................................... 24 Filtering

See Averaging Samples & Averaging Window

Front Panel Controls........................................................... 5-6 Front Panel Programming Codes...................................... 8-9 Main Programming Mode................................................ 8 On Demand Modes......................................................... 9 Setpoint Programming Mode.......................................... 8 View Modes..................................................................... 9

Functional Diagram............................................................. 43 General Features................................................................. 1 Hysteresis and Deviation................................................... 35-89, 01 Initial Setup Procedures..................................................... 10-11 Code Blanking and Macro Check................................... 10-11 Model and Software Code Version Check...................... 10 Input Signal Conditioning Modules Modular Position.............................................................. 45

Index

Linearization

Channel 1 Temperature Sensors.................................... 28 Channel 1 User Loaded Tables....................................... 29 Channel 2 Temperature Sensors

and User Loaded Tables................................................. 30

Channel 3 Temperature Sensors

and User Loaded Tables................................................. 31

Channel 4 Temperature Sensors

and User Loaded Tables................................................. 32 Result of CH1 & CH2 User Loaded Tables..................... 33

Table Settings.................................................................. 13, 33

Macros

Macro Check................................................................... 10-11 Manual Loader..................................................................... 16 Math Function

Cross Channel Math....................................................... 4, 33 Result Processing........................................................... 33 Modbus................................................................................ 13

Model Type Check............................................................... 10 On Demand Functions........................................................ 12

Panel Cutout........................................................................ 50 PID Control Settings........................................................... 36 40 Power Supply...................................................................... 43 Prescaling

Channel 1........................................................................ 28 Channel 2........................................................................ 30 Print Mode............................................................................ 29

Programming Codes........................................................... 8-9 Programming Conventions................................................ 7 Registers

Registers That Can Be Selected..................................... 42 Registers That Should Not Be Selected......................... 42 Resetting and Incrementing Using Setpoints.................. 42 Relay Options...................................................................... 44 Serial Communication

Configuration................................................................... 29

Pinouts............................................................................ 44

Setpoint Programming Mode............................................. 35-41 Data Logging................................................................... 36 Data Printing to PC......................................................... 36 Data Printing to Serial Printer......................................... 36 Display Flashing.............................................................. 36 Hysteresis or Deviation................................................... 36-38, 40

Level 1 - Basic Mode - Prog. Procedures....................... 39 PID Control Settings....................................................... 36, 40

Real-time Clock Option................................................... 36 Real Time Control Modes............................................... 37-38 Relay Energize Functions............................................... 36

Setpoint & Relay Control Settings................................... 35, 40 Setpoint Activation Source.............................................. 36 Setpoint Activation Values............................................... 35 Setpoint Latching............................................................ 36 Setpoint Reset & Trigger................................................. 36, 41 Setpoint Tracking............................................................. 36 Timer Modes................................................................... 36, 41

Smart Input Modules

Setting Up....................................................................... 28

Table of Contents................................................................ 1 Timers.................................................................................. 36

Configuration................................................................... 28, 31, 32

Delay Settings................................................................. 41 Modes............................................................................. 37-38

Totalizers

Setting............................................................................. 12-13

Page 49

Case Dimensions

FRONT VIEW

9/64 DIN

36x144 mm

Panel Adaptor to fit existing 6" Edgewise Pointer Meter Cut-Outs P/N.(OP-PA/144x36)

SIDE VIEW

To open rear cover, use a small flat blade screw driver.

Press down lightly

to release catch and lever outwards.

Two bezel Trim

Strips are supplied with each Panel Adaptor

The adaptor snaps on the 36x144 mm

(1.42"x5.69") case and

enables single unit or stack mounting in an existing 6" edgewise

pointer meter cut-out.

When extra panel

mounting tightness is

required, order the optional

screw mount

clip.

Various

bezel colors

are available.

Black is

standard.

Metal Surround Case:

These dimensions are increased

by 2 mm (0.08") when the

metal surround case

is installed.

Clear Lockable NEMA-4X

Splash Proof Lens Cover P/N.(OP-N4/144X36 )

Metal Surround Case

P/N.(OP-MTL144X36)

is pre-installed at the factory and cannot

be removed without damage to the case.

TOP VIEW

450 State Place Escondido, CA 92029 Tel: 1-760-598-9899 USA 1-800-839-6283 Thats 1-800-TEXMATE Fax: 1-760-598-9828 Email: [email protected] Web: www.texmate.com

Page 50

For product details visit www.texmate.com Local Distributor Address

About TexMate

Texmate is an American manufacturer of high durability industrial grade panel meters, bar graphs, and transducers. Texmate's meters are frequently equipped with relays and various signal outputs for industrial automation applications and are known for their extremely long service life.