Table 1
Output signal:
TT-2D2MM: Two analog output, 0/4~20mA or optional 0~10Vdc TT-2D2MC: One alalog output, 0/4~20mA or optional 0~10Vdc and one RS485
Output resolution: 0.6uA.
Output response time: <200mS.
Load: Max. (VPower supply - 10 V) / 0.020 Power supply: 18 to 36 V, internal protection against polarity inversion.
Communication: Modbus RS485 RTU protocol, 4800~38400 bps Common mode rejection ratio: >80dB.
Galvanic isolation: 2 KV 1min. between input and output Operating temperature: 0 to 55C Humidity: 0 to 90% RH Electromagnetic compatibility (EMC): En 50081-2, En 50082-2 Housing material: ABS plastic. UL 94V0 Weight: 85g
CASE DIMENSIONS
Figure 1
TT-2D2MM and TT-2D2MC are the DIN rail mount user programmable Isolated dual independent channel universal signal converters. It accepts various input signals including mV, V, mA, PT100 and 9 different thermocouples. The measuring unit and range are also configurable with a user-friendly TT Configurator software.
Two independent input channels for various inputt signals and measuring range.
Easy configuration without external power connected.
Dual channel Input:
Resistance thermometer (Pt100)
Thermocouple (J, K, T, E, B, R, S, N, C) Voltage/Current transmitter (mV/V/mA)
Dual analog output: 0/4 to 20mA or optional 0~10V.
RS485 comm. (TT-2D2MC): Modbus RTU protocol.
Fault signal on sensor break presettable.
Specifications
Input signal: User programmable. refer to table 1.
Thermocouple (T/C): Industry standard thermocouple
types, J, K, T, E, B, R, S, N, C (ITS-90).
Pt100: Excitation 180uA. 2 or 3 wire connection (ITS-90 =0.00385).
Voltage: -60mVdc to 60mVdc or -10Vdc to 10Vdc.
Current: 0mA to 24mA Measuring range: User programmable. Max. range see table 1.
Measuring accuracy: Refer to Table 1. The accuracy is tested under the operating condition of 24C3C.
Input sampling rate: 200mS.
Page 1
Wiring Specification:
Screw tightening torque: 4.3 lb-in,
Wire range: 12~30 AWG.
Wire strip length: 6~7mm
Wiring Precaution:
The transmitter is user configurable with the user-frendly TT Configurator software and URC-1020 interface cable. The lastest version can be download free from www.texmate.com.
The URC-1020 Interface cable consist of interface converter and USB plug. It can be purchased separately. During configuration the transmitter can work alone with or without connecting to a power source.
Figure 6
1. Always keep signal wires away from power or contactor wires.
2. Transmitter's power supply should not be shared with
contactors, electrical motor and other inductive devices.
The various input signals are divided into three groups.
1. TC/RTD/mV: Thermocouple type (J, K, T, E, B, R, S, N, C),
The Configurable parameters are:
Figure 5
Pt100 and voltage input in the range of -60mVdc~60mVdc.
1. Input signal type: Various input signal type can be selected
2. Current: 0~24 mA.
3. Voltage: -10~10Vdc.
For the three different groups of input signal type, The SW1 and SW2 should be set according to the Table 2 for each channel separately. Open the cover o change the DIP switch setting.
*Factory setting
Table 2.
Internal DIP switch setting
(1) Downscale (<4mA).
(2) upscale (>20mA).
among the available options.
2. Unit: Select the unit (C or F) of temperature. For linear input
(voltage or current), it doesnt effect the measurement.
3. Measuring range: Defines the lowest and highest value of
measuring range. Within the range, the transmitter will convert input signals into an scalable analogue output signal.
4. Output direction: Defines the scalable analogue
output signal to be 4 to 20mA or 20 to 4mA.
5. Fault signal on sensor break: Defines the output signal to be
(3) Cut-off. Limit the output signal within the output range when the input is out of measuring range.
6. Offset Correction: Allows to eliminate the offset error of
measuring value.
7. ID & Baud Rate: Set device ID and communication baud rate.
8. 0/4~20mA Output Signal Calibration: Zero and Span adjustment of output signal. A power source shoule be connected as Figure 6.
9. Measuring value: Read the measuring value of channel 1
(PV1), channel 2 (PV2) continually.
10. Device information: Indicate the device model, firmware version, series number and communication status. Figure 5.
URC-1020 Interface cable
Mounting
Removing
All the input signals and output current are calibrated within the specified accuracy at factory. Further Custom input and output signal adjustment can be recalibrated with TT Configurator software.
Page 2
Texmate is an American manufacturer of high durability industrial grade panel meters, bar graphs, and transducers. Texmate's meters are frequently equipped with relays and various signal outputs for industrial automation applications and are known for their extremely long service life.